Digital Multi Control

Generator current limit

Notice

This parameter only applies when an external transfer switch is used and has no impact otherwise.

The generator AC current limit can be adjusted within the range of 0 to 198A, with increments of 2A.

When configuring the generator AC current limit, be aware that not all generators can operate at full load. Particularly, smaller 3000 rpm generators from certain brands can overheat during extended full-load operation, and the maximum current should be less than the rated maximum, while the AC current limit for 1500 rpm generators can be set higher.

  • For 3000 rpm generators, set to 70% of their rated maximum.

  • For 1500 rpm generators, set to 90% of their rated maximum.