The inverter has two different types of low battery shutdown modes:

  • Low battery shutdown based on battery voltage. This is the "low battery shutdown" voltage.

  • Low battery shutdown based on battery voltage as a function of battery load. This mode is disabled by default. See next chapter Dynamic cut off for more information.

Once the inverter has shut down due to a low battery (regardless of the mode):

  • The inverter will restart again once the battery voltage has increased above the "low battery restart and alarm" level.

  • The inverter will clear the low battery alarm once it detects the battery is being charged. This is the "charge detect" voltage.

Battery voltage

Low battery shutdown

Low battery restart & alarm

Charge detect

12V

Default: 9.3V

Range: 0-100V

Default: 10.9V

Range: 0-100V

Default: 14V

Range: 0-100V

24V

Default: 18.6V

Range: 0-100V

Default: 21.8V

Range: 0-100V

Default: 28.0V

Range: 0-100V

48V

Default: 37.2V

Range: 0-100V

Default: 36.6V

Range: 0-100V

Default: 56.0V

Range: 0-100V