Pre-VE.Bus scaling factor
Notice
This parameter only applies to pre-VE.Bus systems. Leave it at its default value of 1 for VE.Bus systems.
The scaling factor aligns the control panel AC current with the system AC current and is exclusive to pre-VE.Bus inverter/chargers.
Begin by calculating the scaling factor as directed in this chapter. Afterwards, move on to configuring the scaling factor. For guidance on configuration, consult the Setup menu chapter.
Scaling factor = (NrOfDevices * DeviceType) - 1
DeviceType: 1 = 16A unit, 2 = 30A unit.
NrOfDevices: all units, including the master unit.
One 16A unit: Scaling factor is: (1 * 1) – 1 = 0
Two 30A units in parallel: Scaling factor is: (2 * 2) – 1 = 3
Four 30A units in parallel: Scaling factor is: (4 * 2) – 1 = 7
Six 30A units in 3-phase (2 paralleled units per phase): Scaling factor is: (2 * 2) – 1 = 3
When configuring a non-zero scaling factor in the control panel, do not specify the number of slaves in the VEConfigure software. Instead, set the slave count to zero.
In a split-phase or 3-phase setup, the NrOfDevices reflects the number of devices per phase. So for a 3-phase system consisting of 6 units (2 per phase), the NrOfDevices is 2.