Skip to main content

MultiPlus

Standard settings: ready for use

On delivery, the Multi is set to standard factory values. In general, these settings are suitable for single-unit operation.

Warning

Warning: The standard charging voltage might not be appropriate for your batteries. Consult the manufacturer's documentation or your battery supplier for guidance.

Setting

Default value

Inverter frequency

60 Hz

Input frequency range

55 - 65 Hz

Input voltage range

94 - 143 VAC

Inverter voltage

120 VAC

Stand-alone / parallel / 3-phase

stand-alone

Search mode

off

Ground relay

on

Charger on/off

on

Battery charge algorithm

four-stage adaptive withBatterySafe mode

Charge current

100 % of the maximum charge current

Battery type

Victron Gel Deep Discharge (also suitable for Victron AGM Deep Discharge)

Automatic equalisation charging

off

Absorption voltage

14.4V

Absorption time

up to 8 hours (depending on bulk time)

Float voltage

13.8V

Storage voltage

13.2V (not adjustable)

Repeated absorption time

1 hour

Absorption repeat interval

7 days

Bulk protection

off

AC input current limit

12A (= adjustable current limit for PowerControl andPowerAssist functions)

UPS feature on

on

Dynamic current limiter off

off

Weak AC

off

Boost factor

2

Programmable relay

alarm function