Configuration by DIP switches
Some settings can be changed with DIP switches.
Procedure:
Turn the Multi on, preferably without load and without AC voltage on the input. The Multi will then operate in inverter mode.
Set the DIP switches as required.
Store the settings by moving DIP switch 6 to “on” and back to “off”.
DIP switch 1
Default setting: to operate the product with the “On/Off/Charger Only” switch ds 1: “off” When combined with the Digital Multi Control panel, a VE.Bus Smart dongle, CCGX, Venus GX or alike, DIP switch 1 should also be in the “off” position. Setting for operation with a 3-position remote switch: ds 1: “on” The 3-position switch must be wired to terminal H, see appendix A.
Use only one type of remote control: either a switch or a Digital Multi Control panel.
DIP switch 2 and 3
These DIP switches can be used to set:
Battery charge voltage and Absorption time
Search mode
(For more system settings, use VEConfigure or the VictronConnect app)
DS 2 - DS 3 | Absorption voltage (V) | Float voltage (V) | Storage Voltage (V) | Absorption Time (hours) | Suitable battery types |
---|---|---|---|---|---|
DS 2=off DS 3=off (default) | 14.4 | 13.8 | 13.2 | 8 | Gel Victron deep discharge Gel Exide A200 AGM Victron deep discharge |
DS 2=on DS 3=off | 14.1 | 13.8 | 13.2 | 8 | Gel Victron long life (OPzV) Long Life (OPzV) Gel Exide A600 (OPzV) Gel MK battery Li-ion (LiFePO4) |
DS 2=off DS 3=on | 14.7 | 13.8 | 13.2 | 5 | AGM Victron deep discharge Tubular plate or OPzS batteries in semi-float mode AGM spiral cell |
Dip switch 4
Not used
Dip switch 5
Search Mode off = off on = on
Store the settings by moving DIP switch 6 to “on” and back to “off”.
Example 1 (factory setting) | Example 2 | Example 3 | ||||||
---|---|---|---|---|---|---|---|---|
|
|
| ||||||
1: 3-position switch connected 2,3: GEL 14.4V 4: any position 5: Search mode off 6: Store setting: off→ on→ off | 1: 3-position switch connected 2,3: GEL long life 14.4V (lithium) 4: any position 5: Search mode off 6: Store setting: off→ on→ off | 1: 3-position switch connected 2,3: Tubular plate 15V 4: any position 5: Search mode on 6: Store setting: off→ on→ off |
Example 1 is the factory setting (since factory settings are entered by computer, all DIP switches of a new product are set to “off”).
Store the settings by changing switch DS-6 from off to on, and then back to off. The LEDs “charger” and “alarm” will flash to indicate acceptance of the settings.