hv_battery_compatibility:mg [2026-06-12 14:41] – created guy_stewarthv_battery_compatibility:mg [2026-06-17 10:08] (current) guy_stewart
Line 9: Line 9:
 ===== Use with the HS19 (650 - 1000 V DC) ===== ===== Use with the HS19 (650 - 1000 V DC) =====
  
-  * Modules per string: **14 - 15** (the product allows 1 - 16; 13 or fewer sits below the HS19 range, and 16 modules would reach 934 V max charge, above MG's own 900 V system limit. Verify with MG.)+  * Modules per string: **14 - 15** 
   * Usable voltage range: **672 - 876 V**   * Usable voltage range: **672 - 876 V**
   * Capacity: **165 - 177 kWh** per string   * Capacity: **165 - 177 kWh** per string
-  * FIXME derived from datasheet per-module voltages (48 V cutoff, 58.4 V max charge), not yet verified 
  
-===== Full product specifications (unverified, from manufacturer datasheet) =====+===== Product specifications =====
  
   * Module RS 230: 51.2 V nominal (16S1P LiFePO4), 230 Ah / 11.8 kWh, liquid thermal management   * Module RS 230: 51.2 V nominal (16S1P LiFePO4), 230 Ah / 11.8 kWh, liquid thermal management
Line 24: Line 23:
  
   * Test status: tested and running in field tests   * Test status: tested and running in field tests
-  * FDCan support: Master HV does not support it; Master HV Mk2 does 
  
 ===== Setup guide ===== ===== Setup guide =====
  
-FIXME Setup instructions to be written.+Contact battery manufacturer for setup instructions.
  
hv_battery_compatibility/mg.txt · Last modified: by guy_stewart

Donate Powered by PHP Valid HTML5 Valid CSS Driven by DokuWiki