+ | Fischer Panda generator can be connected to a GX Device, which makes it possible to monitor | ||
+ | |||
+ | The generator needs to be connected to the VE.Can port of the GX Device, which requires a Fischer Panda SAE J1939 module. | ||
+ | |||
+ | ===== Requirements | ||
+ | * [[venus-os: | ||
+ | * Fischer Panda generator, xControl or iGenerator | ||
+ | * Fischer Panda SAE J1939 CAN module (part number 0006107) | ||
+ | * Fischer Panda FP-Bus to VE.Can adapter (part number 0023441) | ||
+ | |||
+ | |||
+ | Fischer Panda Firmware requirements: | ||
+ | * iControl (for the iGenerator): | ||
+ | * iControl panel: no minimum requirement | ||
+ | * xControl (for the constant speed generators): | ||
+ | * xContr panel: 4V29 | ||
+ | * Fischer Panda SAE J1939 CAN module: 2V05 | ||
+ | * Fischer Panda three phase module: 4V0b | ||
+ | ===== Connecting ===== | ||
+ | |||
+ | ==== xControl ==== | ||
+ | The schematic below shows how to connect a Fischer Panda xControl generator. | ||
+ | {{: | ||
+ | |||
+ | ==== iControl ==== | ||
+ | The schematic below shows how to connect a Fischer Panda iControl generator. | ||
+ | {{: | ||
+ | |||
+ | **:!: Important: Operation of the generator is only possible and allowed when the xControl or the iControl panel is switched on. ** | ||
+ | ===== GX Device ===== | ||
+ | |||
+ | In Settings -> Services, the selected canbus profile must be one that says NMEA2000. (The default). | ||
+ | |||
+ | When all wiring is complete and the setup has been correctly carried-out, | ||
+ | |||
+ | {{: | ||
+ | |||
+ | Entering the Fischer Panda device on the menu reveals a page like this: | ||
+ | |||
+ | {{: | ||
+ | |||
+ | Notice that it features an on/off switch as well as displaying status information, | ||
+ | |||
+ | Engine temperature, | ||
+ | |||
+ | {{: | ||
+ | ===== Generator start/stop ===== | ||
+ | In addition to the manual start/stop and monitoring, there is also an automatic start/stop feature. This has the same comprehensive range of options as the Generator start/stop feature associated with the GX relay. | ||
+ | See [[ccgx: | ||
+ | |||
+ | {{: | ||
+ | |||
+ | ===== Maintenance ===== | ||
+ | Whenever performing maintenance on the generator, be sure to //stop// the generator from the Fischer Panda control panel. This will disable the Fischer Panda autostart feature, and ensures that the generator cannot be remotely started - by a CCGX, for example. | ||
+ | |||
+ | When the maintenance is completed, make sure you enable the autostart feature again. You can do this on the Fischer Panda control panel in the menu '' | ||
+ | |||
+ | ===== Troubleshooting ===== | ||
+ | |||
+ | === I've set the mode of the genset to ' | ||
+ | Make sure the Fischer Panda autostart feature is on, this allows the GX control the remote on/off of the genset. You can find this option on the control panel in the menu '' | ||
+ | |||
+ | If you're manually trying to start the genset, a toast message appears with the text '' | ||
+ | {{: | ||
+ | |||
+ | If the generator auto start/stop is enabled, it will show error ''# | ||
+ | {{: | ||
+ | |||