Skip to main content

MultiPlus-II 4k, 4k5, 6k5, 10k 230V

7. Technical specifications

In this section:

MultiPlus-II 230V

12/4k/160-32

48/4k5/55-32

48/6k5/100-50

PowerControl / PowerAssist

Yes

AC input voltage range

Input voltage range: 187 - 265VAC

AC input frequency range

Input frequency: 45 - 65Hz

Maximum feed-through current

32A

32A

50A

Maximum AC input current

32A

32A

50A

INVERTER

DC input voltage range

9,5-17V

38 - 60V

AC output voltage

Output voltage: 230VAC ± 2%

AC output Frequency (1)

50Hz ± 0.1%

Continuous output power at 25°C / 77°F

3,4kW

4kW

6kW

Continuous output power at 40°C / 104°F

3,1kW

3,7kW

5,7kW

Continuous output power at 65°C / 150°F

2,6kW

3kW

4,6kW

Time-limited power 1 (cold start)

4kW/1h

4,5kW/2h

6,5kW/4h

Time-limited power 2 (cold start)

4,5k/2s

6 kW/25min

8kW/1h

Maximum feed-in power

3,4kW

4kW

6kW

Peak power

6kW/30s

7kW/1min

11kW/1min

Maximum efficiency

93%

95%

96%

Zero-load power

18W

20W

28W

Zero-load power in AES mode

11W

13W

18W

Zero-load power in Search mode

4W

8W

8W

CHARGER

AC input voltage range

187 - 265VAC

AC input frequency range

45 - 65Hz

Charge voltage 'absorption'

14,4V

57,6V

Charge voltage 'float'

13,8V

55,2V

Storage mode

13,2V

52,8V

Max. battery charge current at 25 °C (4)

160A

55A

100A

Max. battery charge current at 40 °C

150A

50A

95A

Battery temperature sensor

Yes

Optional. Order number: ASS000001000

Compatible battery chemistries

Lithium, Lead-acid and more (3)

GENERAL

Auxiliary output

Yes (32A)

External AC current sensor (optional)

100A

Programmable relay 

Yes

Protection (2)

a - g

VE.Bus communication port

Three-phase and parallel operation, remote monitoring and system integration

General-purpose communication port

Yes, 2x

Operating temperature range

-40 to +65°C (-40 – 150°F), fan-assisted cooling

Maximum humidity

95% (non-condensing)

Maximum altitude

4000m with 1%/100m power derating above 2000m

ENCLOSURE

Material & Colour

Steel, blue RAL 5012

Protection category

IP 21

Battery connections

Two positive M8 bolts and two negative M8 bolts

One positive M8 bolt and one negative M8 bolt

AC connections

Screw terminals 13mm² (6 AWG)

Weight

22kg

22kg

29kg

Dimensions h x w x d

576 x 276 x 164mm

590 x 275 x 149mm

644 x 320 x 150mm

STANDARDS

Safety

EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1, EN-IEC 62109-2

Emission / Immunity

EN 55014-1, EN 55014-2 EN-IEC 61000-3-2, EN-IEC 61000-3-3 IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3

Uninterruptible power supply

IEC 62040

Anti-islanding

IEC 62116

  1. Can be adjusted to 60Hz

  2. Protection key:

    1. Output short circuit

    2. Overload

    3. Battery voltage too high

    4. Battery voltage too low

    5. Temperature too high

    6. 230 VAC on inverter output

    7. Input voltage ripple too high

3. Other chemistries are possible as well, provided the charger is configured according to the battery manufacturer’s specification.

4. Programmable relay which can be set for general alarm, DC under voltage or generator start/stop function. AC rating: 120V / 4A, DC rating: 4A up to 35VDC and 1A up to 60VDC

MultiPlus-II 230V

48/10k/150-100

PowerControl / PowerAssist

Yes

AC input voltage range

Input voltage range: 187 - 265VAC

AC input frequency range

Input frequency: 45 - 65Hz

Maximum feed-through current

100A

Maximum AC input current

100A

INVERTER

DC input voltage range

42-60V

AC output voltage

Output voltage: 230VAC ± 2%

AC output Frequency (1)

50Hz ± 0.1%

Continuous output power at 25°C / 77°F

10kW

Continuous output power at 40°C / 104°F

9,1kW

Continuous output power at 65°C / 150°F

4,4kW

Time-limited power 1 (cold start)

11kW/3h

Time-limited power 2 (cold start)

12kW/1h

Maximum feed-in power

10kW

Peak power

15kW/2min

Maximum efficiency

93%

Zero-load power

33W

Zero-load power in AES mode

21W

Zero-load power in Search mode

7W

CHARGER

AC input voltage range

187 - 250VAC

AC input frequency range

45 - 65Hz

Charge voltage 'absorption'

57,6V

Charge voltage 'float'

55,2V

Storage mode

52,8V

Max. battery charge current at 25 °C (4)

150A

Max. battery charge current at 40 °C

140A

Battery temperature sensor

Optional. Order number: ASS000001000

Compatible battery chemistries

Lithium, Lead-acid and more (3)

GENERAL

Auxiliary output

Yes (50A)

External AC current sensor (optional)

100A

Programmable relay 

Yes

Protection (2)

a - g

VE.Bus communication port

Three-phase and parallel operation, remote monitoring and system integration

General-purpose communication port

Yes, 2x

Operating temperature range

-40 to +65°C (-40 – 150°F), fan-assisted cooling

Maximum humidity

95% (non-condensing)

Maximum altitude

4000m with 1%/100m power derating above 2000m

ENCLOSURE

Material & Colour

Steel, blue RAL 5012

Protection category

IP 21

Battery connections

Two positive M8 bolts and two negative M8 bolts

AC connections

M6 bolts

Weight

48kg

Dimensions h x w x d

723x360x208mm

STANDARDS

Safety

EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1, EN-IEC 62109-2

Emission / Immunity

EN 55014-1, EN 55014-2 EN-IEC 61000-3-2, EN-IEC 61000-3-3 IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3

Uninterruptible power supply

Anti-islanding

  1. Can be adjusted to 60Hz

  2. Protection key:

    1. Output short circuit

    2. Overload

    3. Battery voltage too high

    4. Battery voltage too low

    5. Temperature too high

    6. 230 VAC on inverter output

    7. Input voltage ripple too high

3. Other chemistries are possible as well, provided the charger is configured according to the battery manufacturer’s specification.

4. Programmable relay which can be set for general alarm, DC under voltage or generator start/stop function. AC rating: 120V / 4A, DC rating: 4A up to 35VDC and 1A up to 60VDC