===== 1. Introduction ===== | ===== 1. Introduction ===== | ||
Line 10: | Line 10: | ||
The AC coupled system sizing guideline, Factor 1.0 rule, from Victron Energy for AC coupled system must be adhered to. | The AC coupled system sizing guideline, Factor 1.0 rule, from Victron Energy for AC coupled system must be adhered to. | ||
- | ===== 2. How to configure ===== | + | ===== 2. How to configure |
+ | |||
+ | Requirements: | ||
+ | |||
+ | * For SetApp (screenless) inverters: Firmware 4.8.24 or higher | ||
+ | |||
+ | * For LCD inverters: Firmware 3.25xx or higher | ||
+ | |||
+ | * Dry-contact for sensing the grid supply. (Victron’s auxiliary Dry-Out can also be used) | ||
+ | |||
+ | * SolarEdge grid meter (required for Zero feedback) | ||
+ | |||
+ | Note: APS mode is mandatory for systems requiring both zero feed-in in on-grid mode and frequency shifting in off-grid mode. | ||
+ | |||
+ | Configuration example 1: Use of external relay and dry contact, see figure 1 | ||
+ | |||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | |||
+ | |||
+ | ;#; | ||
+ | ;#; | ||
+ | Figure 1 | ||
+ | ;#; | ||
+ | |||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | #;; | ||
+ | Configuration example 2: Use of Internal programmable relay K1, See Figure 2 | ||
+ | #;; | ||
+ | |||
+ | ;#; | ||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | ;#; | ||
+ | |||
+ | ;#; | ||
+ | ;#; | ||
+ | Figure 2 | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | Programmable relay K1 Set up | ||
+ | |||
+ | ;#; | ||
+ | ;#; | ||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | ;#; | ||
+ | |||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | __1. Dry contact installation__ | ||
+ | |||
+ | Install a dry contact, sensing the grid availability. Connect twisted pair wires from the dry contact terminals to the L1 and V terminals of the Communication Board inside the inverter, see figure 4. | ||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | ;#; | ||
+ | Figure 4 | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | __2. Alternative Power Source mode__ | ||
+ | |||
+ | Alternative Power Source mode should be configured on the master inverter. Once configured, the master inverter automatically sets all detected slave inverters to Alternative Power Source mode. | ||
+ | |||
+ | To Configure Alternative Power Source mode: | ||
+ | |||
+ | * Commissioning -> Communication -> GPIO -> Power Reduction Interface (RRCR) Mode -> Alternative Power Source. | ||
+ | |||
+ | ;#; | ||
+ | | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | Inverters with LCD | ||
+ | |||
+ | * Enter the inverter’s setup menu using the SolarEdge Password. | ||
+ | |||
+ | * Communication -> GPIO Conf -> Device Type -> Alternative Power Src. | ||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | ===== 3. How to configure Frequency Shifting ===== | ||
+ | |||
+ | |||
+ | Important note: Please ensure the SolarEdge inverter and your VE.Bus Config is set up for the same frequency bandwidth. | ||
+ | |||
+ | **For systems that can feedback into the grid or for pure off-grid systems**: | ||
+ | |||
+ | __1. Enable frequency shifting__ | ||
+ | |||
+ | * Go into Power Control | ||
+ | |||
+ | * Ensure Grid control is Enabled | ||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | | ||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | __2. Configure Wakeup Conf.__ | ||
+ | |||
+ | * Power Control -> Wakeup Profile -> Edit | ||
+ | |||
+ | * Edit Maximum Wake up Frequency = 51.2Hz | ||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | Inverters with LCD: | ||
+ | * Power Control -> Wakeup Profile -> Edit | ||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | __3. Disable Wakeup gradient__ | ||
+ | |||
+ | * Power Control -> Active Power control -> Wakeup Gradient -> Disable | ||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | Inverters with LCD | ||
+ | |||
+ | * Power Control -> Active Power control -> Wakeup Gradie -> Disable | ||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | __4. Set P(F)__ | ||
+ | |||
+ | * Power Control -> Active Power control -> P(f) | ||
+ | |||
+ | * Edit P0: 50.5Hz, 100% Power | ||
+ | |||
+ | * and P1: 51.2Hz, 0% Power | ||
+ | |||
+ | ;#; | ||
+ | | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | Inverters with LCD | ||
+ | |||
+ | * Power Control -> Active Power control -> P(f) | ||
+ | |||
+ | * Edit P0: 50.5Hz, 100% Power | ||
+ | |||
+ | * and P1: 51.2Hz, 0% Power | ||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | **For systems with zero grid feed-in** | ||
+ | |||
+ | In addition to the frequency settings above, please set the following: | ||
+ | |||
+ | __1. Configure P(f) for APS__ | ||
+ | |||
+ | * Power Control -> Alternative Power Source -> P(f) | ||
+ | |||
+ | * Edit P0: 50.5Hz, 100% Power | ||
+ | |||
+ | * and P1: 51.2Hz, 0% Power | ||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | Inverters with LCD | ||
+ | |||
+ | * Power Control -> Alt Power Src-> P(f) | ||
+ | |||
+ | * Edit P0: 50.5Hz, 100% Power | ||
+ | |||
+ | * and P1: 51.2Hz, 0% Power | ||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | ===== 4. Set ESS assistance ===== | ||
+ | |||
+ | |||
+ | The same bandwidth needs to be configured on VE.Bus Config for Victron | ||
+ | |||
+ | Start ESS assistance and set: | ||
+ | |||
+ | - The solar converter will start reducing its output power at 50.2Hz | ||
+ | - Output power will be reduced to a minimum when the frequency is 51.2Hz | ||
+ | - The converter will disconnect when the frequency is higher than 51.5Hz | ||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | ===== 5 How to configure Sunspec to allow inverter monitoring via Victron GX device ===== | ||
+ | |||
- Ensure that the GX Device and the SolarEdge system are both on the same LAN or WiFi network. | - Ensure that the GX Device and the SolarEdge system are both on the same LAN or WiFi network. | ||
- | - Enable ModbusTCP | + | - Enable ModbusTCP |
- | - The Modbus | + | |
- | - On the GX Device, navigate to Settings | + | * Communication -> Modbus TCP port -> Modbus TCP -> Edit port to 502. |
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | Inverters with LCD | ||
+ | |||
+ | | ||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | 3. Enable SunSpec | ||
+ | |||
+ | * Communication -> RS481 -> Protocol -> SunSpec (Non-SE Logger) | ||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | Inverters with LCD | ||
+ | |||
+ | | ||
+ | |||
+ | ;#; | ||
+ | {{: | ||
+ | ;#; | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | Once you are done with the SunSpec setup you can re-configure RS485-1 | ||
- | RS485-1 menu on the Solar Edge, showing | + | **Note:** |
- | {{ : | + | It also advised editing |
- | Details: | ||
- | - The SE2200H - SE6000H range (HD-wave) was specifically tested, though several others are reported to work too. | ||
- | - During testing, we found that the SolarEdge PV Inverter accepts just one concurrent TCP connection. Additional connections are rejected. |
venus-os/gx_solaredge.txt · Last modified: 2021-09-21 16:22 by fjlacock