 ==== Error 18 - AC Over-voltage on the output of a slave while switched off ==== ==== Error 18 - AC Over-voltage on the output of a slave while switched off ====
 Solution: check if AC wires are not swapped by accident. There can never be voltage on the AC out when a unit is switched off.  Solution: check if AC wires are not swapped by accident. There can never be voltage on the AC out when a unit is switched off. 
 +
 +==== Error 19 - Slave does not have AC input! ====
 +
 +Common cause - System is configured with multiple synchronised inverter/​chargers but AC input (e.g. from a generator) is only connected to one of the Inverter/​Chargers.
 +
 +Solution: Either connect the AC input to all units, or change the configuration of the synchronised units in VE.Bus System Configurator (note not VEConfigure),​ and disable the '​Switch as Group' Function. This setting will allow only a single Inverter/​Charger to charge without error. Note this setting is not adjustable in an ESS system.
  