mvader [Error 17 - Phase master missing]
Line 186: Line 186:
   - The most likely cause is a cable-related communication issue on the VE.Bus network: \\ __Solution__: First check the network cables sockets. If that doesn't solve it, replace all network cables, including the cable to the [[venus-os:start|GX Device]]. Make sure to also inspect the female RJ-45 sockets, instead of only the cabling: sometimes badly mounted RJ45 cable connectors prevent the spring-contacts in the female RJ45 connectors on the Multis to properly make contact. Make sure to machine-made cabling. Do not use self-crimped cables.   - The most likely cause is a cable-related communication issue on the VE.Bus network: \\ __Solution__: First check the network cables sockets. If that doesn't solve it, replace all network cables, including the cable to the [[venus-os:start|GX Device]]. Make sure to also inspect the female RJ-45 sockets, instead of only the cabling: sometimes badly mounted RJ45 cable connectors prevent the spring-contacts in the female RJ45 connectors on the Multis to properly make contact. Make sure to machine-made cabling. Do not use self-crimped cables.
   - DC fuse blown. In this case, all units can in some situations seem fine and work well as long as mains is available. And then when there is no longer AC available on the input (mains fails or generator is stopped) the non powered units are disconnected from the system. \\ __Solution__: Check the fuse in all units; replace the broken one.   - DC fuse blown. In this case, all units can in some situations seem fine and work well as long as mains is available. And then when there is no longer AC available on the input (mains fails or generator is stopped) the non powered units are disconnected from the system. \\ __Solution__: Check the fuse in all units; replace the broken one.
-  - Update firmware and Assistants of the inverter/chargers. And of the GX Device. \\ __Solution__: [[updating_firmware:updating_ve.bus_products|Update the Inverter/charger firmware]] - [[assistants:how_to_update_an_assistant|Update the Assistants]] - [[ccgx:firmware_updating|Update the GX Device firmware]].+  - Update firmware and Assistants of the inverter/chargers. And of the GX Device. \\ __Solution__: (1) [[updating_firmware:updating_ve.bus_products|Update the Inverter/charger firmware]] - (2) [[assistants:how_to_update_an_assistant|Update the Assistants]] - (3) [[ccgx:firmware_updating|Update the GX Device firmware]].
  
 === Systems with multiple slaves per phase === === Systems with multiple slaves per phase ===
Line 196: Line 196:
 ==== Error 18 - AC Over-voltage on the output of a slave while switched off ==== ==== Error 18 - AC Over-voltage on the output of a slave while switched off ====
 Solution: check if AC wires are not swapped by accident. There can never be voltage on the AC out when a unit is switched off.  Solution: check if AC wires are not swapped by accident. There can never be voltage on the AC out when a unit is switched off. 
 +
 +==== Error 19 - Slave does not have AC input! ====
 +
 +Common cause - System is configured with multiple synchronised inverter/chargers but AC input (e.g. from a generator) is only connected to one of the Inverter/Chargers.
 +
 +Solution: Either connect the AC input to all units, or change the configuration of the synchronised units in VE.Bus System Configurator (note not VEConfigure), and disable the 'Switch as Group' Function. This setting will allow only a single Inverter/Charger to charge without error. Note this setting is not adjustable in an ESS system.
  
 ==== Error 22 - This device cannot function as a slave ==== ==== Error 22 - This device cannot function as a slave ====