Previous revision
ve.bus:ve.bus_error_codes [2019-06-11 10:20]
mvader [General]
ve.bus:ve.bus_error_codes [2019-06-24 08:08] (current)
mvader [Error 3 - Not all, or more than, the expected devices were found in the system]
Line 39: Line 39:
   - This error often follows VE.Bus Error 1. Solution: solve the cause for VE.Bus Error 1. Note that when using an older CCGX (version before v1.40), ​ it can be that the first error is not reported on the Alarm log on VRM. So even when it only lists VE.Bus Error 3, it can very well be that that error was preceeded by VE.Bus Error 1.   - This error often follows VE.Bus Error 1. Solution: solve the cause for VE.Bus Error 1. Note that when using an older CCGX (version before v1.40), ​ it can be that the first error is not reported on the Alarm log on VRM. So even when it only lists VE.Bus Error 3, it can very well be that that error was preceeded by VE.Bus Error 1.
   - The system is not properly configured: all VE.Bus devices connected to the VE.Bus network must be configured as one parallel, split- and/or three-phase system. Do not connect two separate VE.Bus systems together.   - The system is not properly configured: all VE.Bus devices connected to the VE.Bus network must be configured as one parallel, split- and/or three-phase system. Do not connect two separate VE.Bus systems together.
-  - Communication cable error: ​check the communication cables. +  - Communication cable error: ​Check the communication cables. Make sure to use commercial patch leads and not hand-crimped cables - VE.Bus cabling is very sensitive to physical wiring faults
-  - DC fuse blown of one or more units in the systemWhen mains is available all units seems to work correctly, but as soon as mains fails, or as soon as the system decides to switch to Island mode for any other reason, the non powered units are disconnected from the system.+  - DC fuse blown of one or more units in the systemWhen mains is available all units seems to work correctly, but as soon as mains fails, or as soon as the system decides to switch to Island mode for any other reason, the non powered units are disconnected from the system. 
   ​   ​
 ==== Error 4 - No other device found ==== ==== Error 4 - No other device found ====
Line 176: Line 177:
   * The AC input voltage slowly drops before it is being rejected by the Multis. Typically happens in installations with a generator. Especially when combined with AC loads that increase their current draw when the AC voltage drops: by the time that the inverter/​charger initiates the disconnect, the current through the relays has increased well beyond the ratings, and is too high to open them.\\ __Solution__:​ Make the Multis or Quattros disconnect earlier: increase lower limit of AC input voltage in VEConfigure3. For example to 210 VAC. The factory setting is 180 VAC.   * The AC input voltage slowly drops before it is being rejected by the Multis. Typically happens in installations with a generator. Especially when combined with AC loads that increase their current draw when the AC voltage drops: by the time that the inverter/​charger initiates the disconnect, the current through the relays has increased well beyond the ratings, and is too high to open them.\\ __Solution__:​ Make the Multis or Quattros disconnect earlier: increase lower limit of AC input voltage in VEConfigure3. For example to 210 VAC. The factory setting is 180 VAC.
   * The back-feed relay has a hardware failure \\ __Solution__:​ Replace faulty unit.   * The back-feed relay has a hardware failure \\ __Solution__:​ Replace faulty unit.
-  * The related current measurement circuit is faulty. \\ __Solution__: ​replace ​faulty unit.+  * The related current measurement circuit is faulty. \\ __Solution__: ​Replace ​faulty unit.
  
 __Diagnosing a parallel, multi or split-phase system?__ __Diagnosing a parallel, multi or split-phase system?__
ve.bus/ve.bus_error_codes.1560241254.txt.gz · Last modified: 2019-06-22 06:09 (external edit)