ve.bus:ve.bus_error_codes [2019-05-17 21:00]
mvader [Error 24 - Switch-over system protection initiated]
ve.bus:ve.bus_error_codes [2019-05-18 07:13] (current)
mvader [Error 17 - Original Master Missing]
Line 143: Line 143:
   * Otherwise, the most likely cause is bad cabling/​contacts on the VE.Bus: Check cabling and contacts. Make sure to also inspect the female RJ-45 sockets, instead of only the cabling: Sometimes badly mounted RJ45 cable connectors prevent the spring-contacts in the female RJ45 connectors on the Multis to properly make contact.   * Otherwise, the most likely cause is bad cabling/​contacts on the VE.Bus: Check cabling and contacts. Make sure to also inspect the female RJ-45 sockets, instead of only the cabling: Sometimes badly mounted RJ45 cable connectors prevent the spring-contacts in the female RJ45 connectors on the Multis to properly make contact.
  
-If nothing can be found and the failure persists a hardware error might be the cause. Contact your distributor,​ and also report the exact LED indication of the Master and all slaves in that phase. 
 ==== Error 18 - AC Over-voltage on the output of a slave while switched off ==== ==== Error 18 - AC Over-voltage on the output of a slave while switched off ====
 Solution: check if AC wires are not swapped by accident. There can never be voltage on the AC out when a unit is switched off.  Solution: check if AC wires are not swapped by accident. There can never be voltage on the AC out when a unit is switched off. 