ve.bus:ve.bus_error_codes [2019-10-25 12:29]
guystewart [Error 11 - Relay Test Fault - Installation error or possibly relay failure]
ve.bus:ve.bus_error_codes [2019-12-10 00:44] (current)
guy_stewart
Line 112: Line 112:
 Step 4: Check your Neutral-out connection. In most cases there should be no external connection between ACin-Neutral to ACout-Neutral,​ or to Earth. ​ Step 4: Check your Neutral-out connection. In most cases there should be no external connection between ACin-Neutral to ACout-Neutral,​ or to Earth. ​
  
-In Australia, it is possible if required to install with a connection between Neutral-in and Neutral-out using AS4777.2:​2015. Select either design configuration in the grid code section while programming the MultiPlus-II with firmware 466 and above.+In Australia, it is possible if required to install with a connection between Neutral-in and Neutral-out using AS4777.2:​2015. Select either design configuration in the grid code section while programming the MultiPlus-II with firmware 466 and above.  
 + 
 +{{:​ve.bus:​men_grid_code.jpg?​direct|}} 
 + 
 +After configuration,​ always confirm that the system is safe with routine electrical safety checks in both modes (eg test RCD operation with AC input connected and disconnected).
  
 Step 5: Neutral and line input might be inverted. Check the input connections,​ swap them if needed and retry. In this case, “Failing step: 8” will show. Step 5: Neutral and line input might be inverted. Check the input connections,​ swap them if needed and retry. In this case, “Failing step: 8” will show.