User Tools

Site Tools


ve.bus:ve.bus_error_codes

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
ve.bus:ve.bus_error_codes [2024-04-24 00:32] – [Error 26 - Internal error] mleeftinkve.bus:ve.bus_error_codes [2024-07-03 17:09] (current) – [Error 25 - Incompatible VE.Bus configuration] pba
Line 394: Line 394:
 __Recovery:__ system remains off until restarted. __Recovery:__ system remains off until restarted.
  
-==== Error 25 - Firmware incompatibility ==== +==== Error 25 - Incompatible VE.Bus configuration ==== 
-Make sure to use the same firmware in all devices. +The VE.Bus configuration as configured is not allowed. This can be due to the fact that: 
 +  - Devices with different firmware versions are used.\\ Solution: Make sure to use the same firmware version in all devices. Update all devices to the latest available firmware. Instructions [[updating_firmware:updating_ve.bus_products|here]]. 
 +  - Devices are not compatible with this configuration.\\ Check the **compatibility ID**'s which can be found on the stickers of the units.<sup>1)</sup>\\ A compatibility ID consists of a 4-digit number followed by a letter. (e.g. 2623_B)\\ VE.Bus systems can only be made with devices with identical 4-digit numbers and only devices with the same letter can be put in a single phase.\\ \\ Solution:\\  
 +    * Make sure that the 4-digit number in the compatibility ID of all units in the VE.Bus system is identical . 
 +    * Make sure that units in a single phase (so parallel units) have an identical letter in the compatibility ID.
  
-Solutionupdate all devices to the latest available firmware. Instructions [[updating_firmware:updating_ve.bus_products|here]]. +__Recovery__: system remains off until configured correctly and restarted.
- +
-__Recovery:__ system remains off until restarted.+
  
 +<sup>1)</sup> If there is no compatibility ID on the sticker then the compatibility ID consists of the first 4 digits of the complete firmware number followed by the letter **A**.\\ The one exception to this rule is firmware 2699xxx: If there is no compatibility ID on the sticker then the compatibility ID is 26**2**9_A (instead of 26**9**9_A).
 ==== Error 26 - Internal error ==== ==== Error 26 - Internal error ====
 Should not occur. Switch all equipment off, and then on again; it will then resume operation. Contact Victron Energy if the problem persists. Should not occur. Switch all equipment off, and then on again; it will then resume operation. Contact Victron Energy if the problem persists.
ve.bus/ve.bus_error_codes.txt · Last modified: 2024-07-03 17:09 by pba

Donate Powered by PHP Valid HTML5 Valid CSS Driven by DokuWiki