Line 178: Line 178:
 PV panel isolation resistance too low. PV panel isolation resistance too low.
 Check the PV array cabling and panel isolation, the inverter restarts automatically once the issue is resolved. Check the PV array cabling and panel isolation, the inverter restarts automatically once the issue is resolved.
 +Consider disconnecting the PV array using the PV switch to resume AC operation.
  
 ==== Err 42 - Inverter shutdown (PV isolation) ==== ==== Err 42 - Inverter shutdown (PV isolation) ====
 The ground leakage current in the PV array exceeds the allowed 30mA limit. The ground leakage current in the PV array exceeds the allowed 30mA limit.
 Check the PV array cabling and panel isolation. Check the PV array cabling and panel isolation.
-Check the installation and restart the unit using the power-switch.+Consider disconnecting the PV array using the PV switch to resume AC operation.
  
 ==== Err 43 - Inverter shutdown (Ground Fault) ==== ==== Err 43 - Inverter shutdown (Ground Fault) ====