Applies to SmartSolar/ | Applies to SmartSolar/ | ||
- | The charger detects multiple conflicting network sources, with the same priority, trying to send the same information to the charger. VE.Can and VE.Direct interfaces have both the same priority level, and BLE (using VE.Smart Networking) has a lower priority. | + | To clear the error on the SmartSolar VE.Direct MPPTs update the FW version to v1.48 or higher. |
+ | |||
+ | To clear the error on the SmartSolar/ | ||
+ | Note: Connecting a Solar charger on both VE.Can and VE.Direct is not supported. | ||
+ | |||
+ | The error occur when the charger detects multiple conflicting network sources, with the same priority, trying to send the same information to the charger. VE.Can and VE.Direct interfaces have both the same priority level, and BLE (using VE.Smart Networking) has a lower priority. | ||
Having a higher priority level means that, if the same information (e.g. Battery voltage sense) is being received from both VE.Can and BLE (using VE.Smart Network) by the charger, the information on VE.Can will be used and the one coming from BLE will be ignored. | Having a higher priority level means that, if the same information (e.g. Battery voltage sense) is being received from both VE.Can and BLE (using VE.Smart Network) by the charger, the information on VE.Can will be used and the one coming from BLE will be ignored. | ||
- | Now, if the same information is being received from two interfaces that has the same priority level (as VE.Can and VE.Direct), the charger does not know how to prioritize those, so then error 68 will be triggered. | + | Now, if the same information is being received from two interfaces that has the same priority level (as VE.Can and VE.Direct), the charger does not know how to prioritize those, so then error 68 will be triggered. |
- | To clear the error on the SmartSolar/ | ||
- | Note: Connecting a Solar charger on both VE.Can and VE.Direct is not supported. | ||
- | To clear the error on the SmartSolar VE.Direct MPPTs update the FW version to v1.48 or higher. | ||
==== Err 114 - CPU temperature too high ==== | ==== Err 114 - CPU temperature too high ==== | ||
This error will reset after the CPU has cooled down. | This error will reset after the CPU has cooled down. |