Error recovery: | Error recovery: | ||
* Error 38: First disconnect the solar panels and disconnect the battery. Wait for 3 minutes, then reconnect the battery first and next the panels. | * Error 38: First disconnect the solar panels and disconnect the battery. Wait for 3 minutes, then reconnect the battery first and next the panels. | ||
- | * Error 39: The charger will automatically resume operation once the battery voltage drops below the float level for 1 minute. | + | * Error 39: The charger will automatically resume operation once the battery voltage drops below its maximum voltage setting (normally Equalisation or Absorption voltages), for 250V versions or float voltage |
If the error persists the charge controller is probably faulty. | If the error persists the charge controller is probably faulty. | ||
+ | |||
+ | ==== Err 40 - PV Input failed to shutdown ==== | ||
+ | |||
+ | If the charger is unable to turn off the PV input, it will go into a safe mode in order to protect the battery from over-charging or having a high voltage on the battery terminals. In order to do that, the charger will stop charging and disconnect its own output. The charger will become faulty. | ||
==== Information 65 - Communication warning ==== | ==== Information 65 - Communication warning ==== |