Note that (solar-)chargers automatically configure themselves to be BMS-controlled when they are connected to one; either direct or via a Color Control GX or Venus GX. | Note that (solar-)chargers automatically configure themselves to be BMS-controlled when they are connected to one; either direct or via a Color Control GX or Venus GX. | ||
+ | |||
+ | ==== Err 68 - Network misconfigured ==== | ||
+ | |||
+ | The charger detects multiple conflicting network sources trying to take control of the charger. | ||
+ | |||
+ | Applies to SmartSolar MPPTs and SmartSolar MPPTs VE.Can. | ||
+ | |||
+ | The typical reason for the error to show is that the charger is configured to operate in parallel using our [[https:// | ||
+ | |||
+ | Resolution: disable the parallel operation by connecting VictronConnect, | ||
+ | |||
+ | For SmartSolar MPPT VE.Can only, also make sure its not connected to a [[https:// | ||
+ | |||
+ | Once the conflict is resolved the error will disappear and the charger will resume normal operation, usually within a minute. | ||
+ | |||
+ | |||