Line 110: Line 110:
  
 Note that (solar-)chargers automatically configure themselves to be BMS-controlled when they are connected to one; either direct or via a Color Control GX or Venus GX. Note that (solar-)chargers automatically configure themselves to be BMS-controlled when they are connected to one; either direct or via a Color Control GX or Venus GX.
 +
 +==== Err 68 - Network misconfigured ====
 +
 +The charger detects multiple conflicting network sources trying to take control of the charger.
 +
 +All Smart Solar charger models:
 +
 +  * If the charger is connected to a Venus GX device that takes control of the charger (by sending Charge Voltage Limits to the unit), the charger cannot not be joined to a VE.Smart network as well. In VictronConnect go to settings "VE.Smart networking" and choose "Leave network".
 +
 +VE.CAN Smart Solar chargers only:
 +
 +  * If the charger is connected via VE.CAN to a Venus GX device do not install a VE.Direct cable to a Venus GX device as well. Either disconnect the VE.CAN cable or the VE.Direct cable.
 +
 +Once the conflict is resolved the error will disappear and the charger will resume normal operation, usually within a minute.
 +
 +
  
 ==== Err 114 - CPU temperature too high ==== ==== Err 114 - CPU temperature too high ====
Line 130: Line 146:
   - wait 3 minutes, and power up again.   - wait 3 minutes, and power up again.
   - Reconfigure the charger.   - Reconfigure the charger.
 +
  
  