==== Err 18 - Controller over-current ==== | ==== Err 18 - Controller over-current ==== | ||
This error will auto-reset. | This error will auto-reset. | ||
- | Disconnect | + | If the error does not auto-reset disconnect |
- | If the error persists the charge controller is probably faulty. | + | A cause for this error can be switching on a very large load on the battery side. |
==== Err 20 - Maximum Bulk-time exceeded ==== | ==== Err 20 - Maximum Bulk-time exceeded ==== | ||
Line 58: | Line 58: | ||
This error will auto-reset. | This error will auto-reset. | ||
+ | |||
+ | ==== Err 28 - Power stage issue ==== | ||
+ | |||
+ | This error will not auto-reset. | ||
+ | |||
+ | Disconnect all wires, and then reconnect all wires. If the error persists the charge controller is probably faulty. | ||
==== Err 33 - PV over-voltage ==== | ==== Err 33 - PV over-voltage ==== | ||
Line 67: | Line 73: | ||
Disconnect the charger from all power-sources, | Disconnect the charger from all power-sources, | ||
- | ==== Err 38 - Input shutdown | + | ==== Err 38, Err 39 - PV Input shutdown ==== |
- | To protect the battery from over-charging the panel input is shorted. To recover from this condition first disconnect the solar panels and disconnect the battery. Wait for 3 minutes, then reconnect the battery first and next the panels. | + | To protect the battery from over-charging the panel input is shorted. |
- | A common reason | + | Possible reasons |
+ | * The Battery voltage (12/24/48V) is set, or auto-detected, | ||
+ | * There is another device connected to the battery, which is configured to a higher voltage. For example a MultiPlus, configured to equalise at 17 Volts, while in the MPPT this is not configured. | ||
+ | * The battery is disconnected using a manual switch. Ideally the charger should be switched off before disconnecting the battery, this avoids a voltage overshoot on the charger output. If necessary the voltage trip-level for the PV Short protection can be increased by raising the Equalization voltage set-point (note: equalization does not have to be enabled in this case). | ||
+ | * The battery is disconnected using a Lithium charge relay connected to the “allow-to-charge” output of a BMS. Consider wiring this signal to the Remote terminal of the charger instead. This shuts down the charger gracefully without creating a voltage overshoot. | ||
- | Another reason is that there is another device connected to the battery, which is configured to a higher voltage. For example a MultiPlus, configured to equalise at 17 Volts, while in the MPPT | + | Error recovery: |
+ | * Error 38: First disconnect the solar panels and disconnect | ||
+ | * Error 39: The charger will automatically resume operation once the battery voltage drops below the float level for 1 minute. | ||
If the error persists the charge controller is probably faulty. | If the error persists the charge controller is probably faulty. | ||
Line 105: | Line 117: | ||
==== Err 116 - Calibration data lost ==== | ==== Err 116 - Calibration data lost ==== | ||
- | The unit is faulty, contact your dealer for a replacement. | + | If the unit does not work and error 116 pops up as the active error the unit is faulty, contact your dealer for a replacement. |
+ | |||
+ | If the error is only present in the history data and the unit operates normally this error can be ignored safely. Explanation: | ||
==== Err 119 - Settings data lost ==== | ==== Err 119 - Settings data lost ==== | ||