====== MPPT Solar Charger Error Codes ====== | ====== MPPT Solar Charger Error Codes ====== | ||
+ | Solar Chargers indicate an error with their LEDs. See the [[https:// | ||
- | ==== Error Codes ==== | + | Detailed error codes can be read with a remote panel, such as the Color Control GX or the MPPT Control. |
- | === Err 2 - Battery voltage too high === | + | ===== Error Codes ===== |
+ | |||
+ | ==== Err 2 - Battery voltage too high ==== | ||
This error will auto-reset after the battery voltage has dropped. | This error will auto-reset after the battery voltage has dropped. | ||
This error can be due to other charging equipment connected to the battery or a fault in the charge controller. | This error can be due to other charging equipment connected to the battery or a fault in the charge controller. | ||
- | === Err 17 - Controller overheated despite reduced output current === | + | This error can also occur if the battery voltage is set to a lower voltage than the actual battery voltage. |
+ | ==== Err 3, Err 4 - Remote temperature sensor failure ==== | ||
+ | Check if the T-sense connector is properly connected to a remote temperature sensor. | ||
+ | Most likely cause: the remote T-sense connector is connected to the BAT+ or BAT- terminal. | ||
+ | This error will auto-reset after proper connection. | ||
+ | |||
+ | ==== Err 5 - Remote temperature sensor failure (connection lost) ==== | ||
+ | Check if the T-sense connector is properly connected to a remote temperature sensor. | ||
+ | This error will not auto-reset. | ||
+ | |||
+ | ==== Err 6, Err 7 - Remote battery voltage sense failure ==== | ||
+ | Check if the V-sense connector is properly connected to the battery terminals. | ||
+ | Most likely cause: the remote V-sense connector is connected in reverse polarity to the BAT+ or BAT- terminals. | ||
+ | |||
+ | ==== Err 8 - Remote battery voltage sense failure (connection lost) ==== | ||
+ | Check if the V-sense connector is properly connected to the battery terminals. | ||
+ | |||
+ | ==== Err 17 - Controller overheated despite reduced output current | ||
This error will auto-reset after charger has cooled down. | This error will auto-reset after charger has cooled down. | ||
Check the ambient temperature and check for obstructions near the heatsink. | Check the ambient temperature and check for obstructions near the heatsink. | ||
- | === Err 18 - Controller over-current === | + | ==== Err 18 - Controller over-current |
This error will auto-reset. | This error will auto-reset. | ||
- | Disconnect | + | If the error does not auto-reset disconnect |
- | If the error persists the charge controller is probably faulty. | + | A cause for this error can be switching on a very large load on the battery side. |
- | === Err 20 - Maximum Bulk-time exceeded === | + | ==== Err 20 - Maximum Bulk-time exceeded |
This error can only occur when the maximun bulk-time protection is active. | This error can only occur when the maximun bulk-time protection is active. | ||
This error will not auto-reset. | This error will not auto-reset. | ||
Line 27: | Line 47: | ||
Our advice is to not enable it on solar chargers. | Our advice is to not enable it on solar chargers. | ||
- | === Err 21 - Current sensor issue === | + | ==== Err 21 - Current sensor issue ==== |
- | The charge controller is probably faulty. | + | |
This error will not auto-reset. | This error will not auto-reset. | ||
- | === Err 26 - Terminal overheated === | + | Disconnect all wires, and then reconnect all wires. Also, make sure the minus on the MPPT charge controller (PV minus/ |
- | Power terminals overheated, check wiring and fasten bolts if possible. | + | |
+ | If the error remains, please contact the dealer, there might be a hardware defect. | ||
+ | ==== Err 26 - Terminal overheated | ||
+ | Power terminals overheated, check wiring, including the wiring type and type of strands, | ||
This error will auto-reset. | This error will auto-reset. | ||
- | === Err 33 - PV over-voltage === | + | ==== Err 33 - PV over-voltage |
This error will auto-reset after PV-voltage has dropped to safe limit. | This error will auto-reset after PV-voltage has dropped to safe limit. | ||
This error is an indication that the PV-array configuration with regard to open-circuit voltage is critical for this charger. Check configuration, | This error is an indication that the PV-array configuration with regard to open-circuit voltage is critical for this charger. Check configuration, | ||
- | === Err 34 - PV over-current === | + | ==== Err 34 - PV over-current |
The current from the solar-panel array has exceeded 75A. This error could be generated due to an internal system fault. | The current from the solar-panel array has exceeded 75A. This error could be generated due to an internal system fault. | ||
- | Disconnect the charger from all power-sources, | + | Disconnect the charger from all power-sources, |
- | This error will auto-reset. | + | |
- | === Err 38 - Input shutdown | + | ==== Err 38, Err 39 - PV Input shutdown |
- | To protect the battery from over-charging the panel input is shut down. To recover from this condition first disconnect the solar panels and disconnect the battery. Wait for 3 minutes reconnect the battery first and next the panels. If the error persists the charge controller is probably faulty. | + | To protect the battery from over-charging the panel input is shorted. |
- | === Information 65 - Communication warning === | + | Possible reasons for this error to occur: |
+ | * The Battery voltage (12/24/48V) is set, or auto-detected, | ||
+ | * There is another device connected to the battery, which is configured to a higher voltage. For example a MultiPlus, configured to equalise at 17 Volts, while in the MPPT this is not configured. | ||
+ | * The battery is disconnected using a manual switch. Ideally the charger should be switched off before disconnecting the battery, this avoids a voltage overshoot on the charger output. If necessary the voltage trip-level for the PV Short protection can be increased by raising the Equalization voltage set-point (note: equalization does not have to be enabled in this case). | ||
+ | * The battery is disconnected using a Lithium charge relay connected to the “allow-to-charge” output of a BMS. Consider wiring this signal to the Remote terminal of the charger instead. This shuts down the charger gracefully without creating a voltage overshoot. | ||
+ | |||
+ | Error recovery: | ||
+ | * Error 38: First disconnect the solar panels and disconnect the battery. Wait for 3 minutes, then reconnect the battery first and next the panels. | ||
+ | * Error 39: The charger will automatically resume operation once the battery voltage drops below the float level for 1 minute. | ||
+ | |||
+ | If the error persists the charge controller is probably faulty. | ||
+ | |||
+ | ==== Information 65 - Communication warning | ||
Communication with one of the paralleled controllers was lost. To clear the warning, switch the controller off and back on | Communication with one of the paralleled controllers was lost. To clear the warning, switch the controller off and back on | ||
- | === Information 66 - Incompatible device === | + | ==== Information 66 - Incompatible device |
The controller is being paralleled to another controller that has different settings and/or a different charge algorithm. | The controller is being paralleled to another controller that has different settings and/or a different charge algorithm. | ||
Line 56: | Line 91: | ||
- | === Error 67 - No BMS === | + | ==== Err 67 - BMS Connection lost ==== |
- | The charger is configured to be controlled by a BMS, but it does not receive any control messages from a BMS. | + | The charger is configured to be controlled by a BMS, but it does not receive any control messages from a BMS. The charger stopped charging, as a safety precaution. |
Check the connection between the charger and the BMS. | Check the connection between the charger and the BMS. | ||
- | Or, when the charger | + | __How to reset the charger, to de-couple it from the BMS__ |
- | Note that (solar-)chargers automatically configure themselves | + | When the charger needs to operate in stand-alone mode again, not controlled |
- | === Error 114 - CPU temperature | + | * VE.Can solar chargers, go into the setup menu, and change setting ‘BMS’ from ‘Y’ to ‘N’ (setup item 31). |
+ | * VE.Direct solar chargers, reset the charger to factory defaults with VictronConnect, | ||
+ | |||
+ | Note that (solar-)chargers automatically configure themselves to be BMS-controlled when they are connected to one; either direct or via a Color Control GX or Venus GX. | ||
+ | |||
+ | ==== Err 114 - CPU temperature | ||
This error will reset after the CPU has cooled down. | This error will reset after the CPU has cooled down. | ||
If the error persists, check the ambient temperature and check for obstructions near the air inlet and outlet holes of the charger cabinet. | If the error persists, check the ambient temperature and check for obstructions near the air inlet and outlet holes of the charger cabinet. | ||
Check manual for mounting instructions with regard to cooling. If error persists the controller is probably faulty. | Check manual for mounting instructions with regard to cooling. If error persists the controller is probably faulty. | ||
- | === Error 116 - Calibration data lost === | + | ==== Err 116 - Calibration data lost ==== |
- | The unit is faulty, contact | + | If the unit does not work and error 116 pops up as the active error the unit is faulty, contact |
+ | |||
+ | If the error is only present in the history data and the unit operates normally this error can be ignored safely. Explanation: | ||
- | === Error 119 - Settings data lost === | + | ==== Err 119 - Settings data lost ==== |
The charger cannot read its configuration, | The charger cannot read its configuration, | ||
mppt-error-codes.txt · Last modified: 2024-02-12 05:48 by guy_stewart