====== MPPT Solar Charger Error Codes ====== | ====== MPPT Solar Charger Error Codes ====== | ||
+ | Solar Chargers indicate an error with their LEDs. See the [[https:// | ||
- | ==== Error Codes ==== | + | Detailed error codes can be read with a remote panel, such as the Color Control GX or the MPPT Control. |
- | === Err 2 - Battery voltage too high (> | + | ===== Error Codes ===== |
+ | |||
+ | ==== Err 2 - Battery voltage too high ==== | ||
This error will auto-reset after the battery voltage has dropped. | This error will auto-reset after the battery voltage has dropped. | ||
This error can be due to other charging equipment connected to the battery or a fault in the charge controller. | This error can be due to other charging equipment connected to the battery or a fault in the charge controller. | ||
- | === Err 17 - Controller overheated despite reduced output current === | + | This error can also occur if the battery voltage is set to a lower voltage than the actual battery voltage. |
+ | ==== Err 3, Err 4 - Remote temperature sensor failure ==== | ||
+ | Check if the T-sense connector is properly connected to a remote temperature sensor. | ||
+ | Most likely cause: the remote T-sense connector is connected to the BAT+ or BAT- terminal. | ||
+ | This error will auto-reset after proper connection. | ||
+ | |||
+ | ==== Err 5 - Remote temperature sensor failure (connection lost) ==== | ||
+ | Check if the T-sense connector is properly connected to a remote temperature sensor. | ||
+ | This error will not auto-reset. | ||
+ | |||
+ | ==== Err 6, Err 7 - Remote battery voltage sense failure ==== | ||
+ | Check if the V-sense connector is properly connected to the battery terminals. | ||
+ | Most likely cause: the remote V-sense connector is connected in reverse polarity to the BAT+ or BAT- terminals. | ||
+ | |||
+ | ==== Err 8 - Remote battery voltage sense failure (connection lost) ==== | ||
+ | Check if the V-sense connector is properly connected to the battery terminals. | ||
+ | |||
+ | ==== Err 17 - Controller overheated despite reduced output current | ||
This error will auto-reset after charger has cooled down. | This error will auto-reset after charger has cooled down. | ||
Check the ambient temperature and check for obstructions near the heatsink. | Check the ambient temperature and check for obstructions near the heatsink. | ||
- | === Err 18 - Controller over-current === | + | ==== Err 18 - Controller over-current |
This error will auto-reset. | This error will auto-reset. | ||
- | Disconnect | + | If the error does not auto-reset disconnect |
- | If the error persists the charge controller is probably faulty. | + | A cause for this error can be switching on a very large load on the battery side. |
- | === Err 20 - Maximum Bulk-time exceeded === | + | ==== Err 20 - Maximum Bulk-time exceeded |
This error can only occur when the maximun bulk-time protection is active. | This error can only occur when the maximun bulk-time protection is active. | ||
This error will not auto-reset. | This error will not auto-reset. | ||
This error is generated when the battery-absorption-voltage is not reached after 10 hours of charging. | This error is generated when the battery-absorption-voltage is not reached after 10 hours of charging. | ||
- | This protection is default: | + | This protection is default |
- | * Solar Chargers | + | |
- | * Solar Chargers with VE.Can connection: same as above. | + | It is default enabled |
- | * Skylla-i: default enabled (dipswitch). Only disable it when using this charger on a relatively large battery bank, where charging the bank will take more than 10 hourrs. | + | |
- | * Skylla IP44: default disabled (settable in the LCD menu). | + | Our advice is to not enable it on solar chargers. |
+ | |||
+ | ==== Err 21 - Current sensor issue ==== | ||
- | === Err 21 - Current sensor issue === | ||
- | The charge controller is probably faulty. | ||
This error will not auto-reset. | This error will not auto-reset. | ||
- | === Err 26 - Terminal overheated === | + | Disconnect all wires, and then reconnect all wires. Also, make sure the minus on the MPPT charge controller (PV minus/ |
- | Power terminals overheated, check wiring and fasten bolts if possible. | + | |
+ | If the error remains, please contact the dealer, there might be a hardware defect. | ||
+ | ==== Err 26 - Terminal overheated | ||
+ | Power terminals overheated, check wiring, including the wiring type and type of strands, | ||
This error will auto-reset. | This error will auto-reset. | ||
- | === Err 33 - PV over-voltage === | + | ==== Err 28 - Power stage issue ==== |
+ | |||
+ | This error will not auto-reset. | ||
+ | |||
+ | Disconnect all wires, and then reconnect all wires. If the error persists the charge controller is probably faulty. | ||
+ | |||
+ | ==== Err 33 - PV over-voltage | ||
This error will auto-reset after PV-voltage has dropped to safe limit. | This error will auto-reset after PV-voltage has dropped to safe limit. | ||
This error is an indication that the PV-array configuration with regard to open-circuit voltage is critical for this charger. Check configuration, | This error is an indication that the PV-array configuration with regard to open-circuit voltage is critical for this charger. Check configuration, | ||
- | === Err 34 - PV over-current === | + | ==== Err 34 - PV over-current |
The current from the solar-panel array has exceeded 75A. This error could be generated due to an internal system fault. | The current from the solar-panel array has exceeded 75A. This error could be generated due to an internal system fault. | ||
- | Disconnect the charger from all power-sources, | + | Disconnect the charger from all power-sources, |
- | This error will auto-reset. | + | |
- | === Err 38 - Input shutdown | + | ==== Err 38, Err 39 - PV Input shutdown |
- | To protect the battery from over-charging the panel input is shut down. To recover from this condition first disconnect the solar panels and disconnect the battery. Wait for 3 minutes reconnect the battery first and next the panels. If the error persists the charge controller is probably faulty. | + | To protect the battery from over-charging the panel input is shorted. |
- | === Information 65 - Communication warning === | + | Possible reasons for this error to occur: |
+ | * The Battery voltage (12/24/48V) is set, or auto-detected, | ||
+ | * There is another device connected to the battery, which is configured to a higher voltage. For example a MultiPlus, configured to equalise at 17 Volts, while in the MPPT this is not configured. | ||
+ | * The battery is disconnected using a manual switch. Ideally the charger should be switched off before disconnecting the battery, this avoids a voltage overshoot on the charger output. If necessary the voltage trip-level for the PV Short protection can be increased by raising the Equalization voltage set-point (note: equalization does not have to be enabled in this case). | ||
+ | * The battery is disconnected using a Lithium charge relay connected to the “allow-to-charge” output of a BMS. Consider wiring this signal to the Remote terminal of the charger instead. This shuts down the charger gracefully without creating a voltage overshoot. | ||
+ | |||
+ | Error recovery: | ||
+ | * Error 38: First disconnect the solar panels and disconnect the battery. Wait for 3 minutes, then reconnect the battery first and next the panels. | ||
+ | * Error 39: The charger will automatically resume operation once the battery voltage drops below the float level for 1 minute. | ||
+ | |||
+ | If the error persists the charge controller is probably faulty. | ||
+ | |||
+ | ==== Information 65 - Communication warning | ||
Communication with one of the paralleled controllers was lost. To clear the warning, switch the controller off and back on | Communication with one of the paralleled controllers was lost. To clear the warning, switch the controller off and back on | ||
- | === Information 66 - Incompatible device === | + | ==== Information 66 - Incompatible device |
The controller is being paralleled to another controller that has different settings and/or a different charge algorithm. | The controller is being paralleled to another controller that has different settings and/or a different charge algorithm. | ||
Line 56: | Line 97: | ||
- | === Error 67 - No BMS === | + | ==== Err 67 - BMS Connection lost ==== |
- | Connection | + | The charger is configured |
+ | Check the connection between the charger and the BMS. | ||
- | 2 mogelijke oorzaken: | + | __How to reset the charger, to de-couple it from the BMS__ |
- | - de bms is er geweest en daarna ' | + | |
- | - men heeft per abuis de optie bms present op ' | + | |
- | === Error 114 - CPU temperature | + | When the charger needs to operate in stand-alone mode again, not controlled by a BMS, it needs to be reset: |
+ | |||
+ | * VE.Can solar chargers, go into the setup menu, and change setting ‘BMS’ from ‘Y’ to ‘N’ (setup item 31). | ||
+ | * VE.Direct solar chargers, reset the charger to factory defaults with VictronConnect, | ||
+ | |||
+ | Note that (solar-)chargers automatically configure themselves to be BMS-controlled when they are connected to one; either direct or via a Color Control GX or Venus GX. | ||
+ | |||
+ | ==== Err 68 - Network misconfigured ==== | ||
+ | |||
+ | The charger detects multiple conflicting network sources trying to take control of the charger. | ||
+ | |||
+ | Applies to SmartSolar MPPTs and SmartSolar MPPTs VE.Can. | ||
+ | |||
+ | The typical reason for the error to show is that the charger is configured to operate in parallel using our [[https:// | ||
+ | |||
+ | Resolution: disable the parallel operation by connecting VictronConnect, | ||
+ | |||
+ | For SmartSolar MPPT VE.Can only, also make sure its not connected to a [[https:// | ||
+ | |||
+ | Once the conflict is resolved the error will disappear and the charger will resume normal operation, usually within a minute. | ||
+ | |||
+ | |||
+ | |||
+ | ==== Err 114 - CPU temperature | ||
This error will reset after the CPU has cooled down. | This error will reset after the CPU has cooled down. | ||
If the error persists, check the ambient temperature and check for obstructions near the air inlet and outlet holes of the charger cabinet. | If the error persists, check the ambient temperature and check for obstructions near the air inlet and outlet holes of the charger cabinet. | ||
Check manual for mounting instructions with regard to cooling. If error persists the controller is probably faulty. | Check manual for mounting instructions with regard to cooling. If error persists the controller is probably faulty. | ||
- | === Error 116 - Calibration data lost === | + | ==== Err 116 - Calibration data lost ==== |
- | The unit is faulty, contact | + | If the unit does not work and error 116 pops up as the active error the unit is faulty, contact |
+ | |||
+ | If the error is only present in the history data and the unit operates normally this error can be ignored safely. Explanation: | ||
+ | |||
+ | SmartSolar models (not the BlueSolar models): upgrading to v1.4x firmware is a one-way trip, you cannot go back to an older firmware version once you upgrade to v1.4x. Reverting to older firmware gives error 116 (calibration data lost), this can be fixed by re-installing the v1.4x firmware. | ||
+ | ==== Err 119 - Settings data lost ==== | ||
+ | The charger cannot read its configuration, | ||
+ | |||
+ | This error will not auto-reset. To get it working again: | ||
+ | - First, restore it to factory defaults. | ||
+ | - Disconnect the charge controller from all power-sources | ||
+ | - wait 3 minutes, and power up again. | ||
+ | - Reconfigure the charger. | ||
- | === Error 119 - Settings data lost === | ||
- | This error will not auto-reset. | ||
- | Restore defaults in the setup menu (setup item 62). | ||
- | Disconnect the charge controller from all power-sources, | ||