| If the charger is unable to turn off the PV input, it will go into a safe mode in order to protect the battery from over-charging or having a high voltage on the battery terminals. In order to do that, the charger will stop charging and disconnect its own output. The charger will become faulty. | If the charger is unable to turn off the PV input, it will go into a safe mode in order to protect the battery from over-charging or having a high voltage on the battery terminals. In order to do that, the charger will stop charging and disconnect its own output. The charger will become faulty. | ||
| - | ==== Err 41 - Inverter shutdown (PV isolation) ==== | + | ==== Err 41 - PV isolation |
| PV panel isolation resistance too low. | PV panel isolation resistance too low. | ||
| - | Check the PV array cabling and panel isolation, the inverter restarts automatically once the issue is resolved. | + | Check the PV array cabling and panel isolation. |
| - | Consider disconnecting the PV array using the PV switch to resume AC operation. | + | |
| + | === Inverters or Multis === | ||
| + | The inverter restarts automatically once the issue is resolved. | ||
| + | Consider disconnecting the PV array using the PV switch to immediately | ||
| + | |||
| + | === Solar Chargers === | ||
| + | The isolated battery charger remains operational. | ||
| + | Once the issue is resolved restart the charger to clear this warning. | ||
| - | ==== Err 42 - Inverter shutdown (PV isolation) ==== | + | ==== Err 42 - PV isolation |
| The ground leakage current in the PV array exceeds the allowed 30mA limit. | The ground leakage current in the PV array exceeds the allowed 30mA limit. | ||
| Check the PV array cabling and panel isolation. | Check the PV array cabling and panel isolation. | ||
| Consider disconnecting the PV array using the PV switch to resume AC operation. | Consider disconnecting the PV array using the PV switch to resume AC operation. | ||
| - | ==== Err 43 - Inverter shutdown (Ground | + | ==== Err 43 - Ground |
| The voltage difference between Neutral and Ground is too high. | The voltage difference between Neutral and Ground is too high. | ||
| - | Inverter or Multi (not connected to the grid): | + | === Inverter or Multi (not connected to the grid) === |
| * The internal ground relay is activated but the voltage over the relay is too high. The relay might be damaged. | * The internal ground relay is activated but the voltage over the relay is too high. The relay might be damaged. | ||
| - | Multi (connected to the grid): | + | === Multi (connected to the grid) === |
| * The ground wire in the installation is not present or not connected properly. | * The ground wire in the installation is not present or not connected properly. | ||
| * Line and Neutral are swapped in the installation. | * Line and Neutral are swapped in the installation. | ||