Both sides previous revisionPrevious revision
hv_battery_compatibility:pylontech [2026-06-23 13:25] – [Use with the HS19 (650 - 1000 V DC)] guy_stewarthv_battery_compatibility:pylontech [2026-06-26 12:50] (current) – [Use with the HS19 (650 - 1000 V DC)] guy_stewart
Line 13: Line 13:
   * Modules per stack: **7 or 8** (the Pylontech product documentation allows 2 - 7; 6 or fewer sits below the HS19 voltage range, Pylontech permits either 7 or 8 to be used with Victron HS19)   * Modules per stack: **7 or 8** (the Pylontech product documentation allows 2 - 7; 6 or fewer sits below the HS19 voltage range, Pylontech permits either 7 or 8 to be used with Victron HS19)
   * Usable voltage range: **650 - 920 V**. A 7 module stack discharge floor is 649 V (estimated at 2.9 V/cell).   * Usable voltage range: **650 - 920 V**. A 7 module stack discharge floor is 649 V (estimated at 2.9 V/cell).
-  * Capacity: **36 kWh** per stack+  * Capacity: 36 kWh per 7 module stack or 41 kWh per 8 modules stack. 
  
 ==== Product specifications ==== ==== Product specifications ====
hv_battery_compatibility/pylontech.1782213904.txt.gz · Last modified: by guy_stewart