Previous revision
hv_battery_compatibility:pylontech [2026-06-23 10:42] – [Full product specifications (unverified, from manufacturer documents)] guy_stewarthv_battery_compatibility:pylontech [2026-06-26 12:50] (current) – [Use with the HS19 (650 - 1000 V DC)] guy_stewart
Line 11: Line 11:
 ==== Use with the HS19 (650 - 1000 V DC) ==== ==== Use with the HS19 (650 - 1000 V DC) ====
  
-  * Modules per stack: **7 only** (the product allows 2 - 7; 6 or fewer sits below the HS19 range) +  * Modules per stack: **7 or 8** (the Pylontech product documentation allows 2 - 7; 6 or fewer sits below the HS19 voltage range, Pylontech permits either 7 or 8 to be used with Victron HS19
-  * Usable voltage range: **650 - 818 V**. The battery's own discharge floor is approx. 605 V (estimated at 2.V/cell), below the HS19 minimum, so the bottom of the SOC range is not available.  +  * Usable voltage range: **650 - 920 V**. A 7 module stack discharge floor is 649 V (estimated at 2.V/cell). 
-  * Capacity: **36 kWh** per stack+  * Capacity: 36 kWh per 7 module stack or 41 kWh per 8 modules stack. 
  
 ==== Product specifications ==== ==== Product specifications ====
hv_battery_compatibility/pylontech.1782204165.txt.gz · Last modified: by guy_stewart