hv_battery_compatibility:pylontech [2026-06-12 14:33] – created guy_stewarthv_battery_compatibility:pylontech [2026-06-17 09:59] (current) guy_stewart
Line 12: Line 12:
  
   * Modules per stack: **7 only** (the product allows 2 - 7; 6 or fewer sits below the HS19 range)   * Modules per stack: **7 only** (the product allows 2 - 7; 6 or fewer sits below the HS19 range)
-  * Usable voltage range: **650 - 818 V**. The battery's own discharge floor is approx. 605 V (estimated at 2.7 V/cell), below the HS19 minimum, so the bottom of the SOC range is unusable+  * Usable voltage range: **650 - 818 V**. The battery's own discharge floor is approx. 605 V (estimated at 2.7 V/cell), below the HS19 minimum, so the bottom of the SOC range is not available
   * Capacity: **36 kWh** per stack   * Capacity: **36 kWh** per stack
  
Line 23: Line 23:
  
   * Test status: will be tested soon   * Test status: will be tested soon
-  * FDCan support: only up to 500 kbit/s (status 04-2024, update requested) 
  
-===== Powercube H2 (deprecated) ===== 
- 
-==== Not for use with the HS19 ==== 
- 
-Maximum stack voltage is 648 V at 12 modules, below the HS19 minimum of 650 V. No valid configuration exists. Not compatible with current HS19 hardware. 
  
  
  