   - When discharge is not allowed -and- loads on AC-Out force the Multi/Quattro to exceed the AC input current limit.  Reasons for not allowing discharge: BMS blocks discharge (DCL=0), or battery SOC level is below the 'minimum SOC' setting in ESS, when SOC is at least 3% above the set level, discharge is allowed again.   - When discharge is not allowed -and- loads on AC-Out force the Multi/Quattro to exceed the AC input current limit.  Reasons for not allowing discharge: BMS blocks discharge (DCL=0), or battery SOC level is below the 'minimum SOC' setting in ESS, when SOC is at least 3% above the set level, discharge is allowed again.
   - A grid code is in use that requires the enabling of battery discharging by aux-inputs. Check the used grid-code in VEConfigure and compare with the electrical signals provided to the Inverter/charger in its AUX inputs.   - A grid code is in use that requires the enabling of battery discharging by aux-inputs. Check the used grid-code in VEConfigure and compare with the electrical signals provided to the Inverter/charger in its AUX inputs.
 +  - The Loss of Mains detection (LOM) causes issues, often in combination with a high impedance connectivity to the utility. For details see [[ve.bus:grid-codes-and-loss-of-mains-detection|]].
  
 === Q5: How can I suppress low battery warnings? === === Q5: How can I suppress low battery warnings? ===
Line 913: Line 913:
  
 __Lastly__, check that the rocker switch on the unit is set to On, rather than to Charger-Only. When set to charger-only, the unit refuses to discharge the battery. Note that to check this, you really need to physically check the rocker switch: you can't see its state by looking on VRM or on the GX Device. On a MultiPlus-II, this rocker switch is at the bottom of the unit and needs to be in the I position, not on II. __Lastly__, check that the rocker switch on the unit is set to On, rather than to Charger-Only. When set to charger-only, the unit refuses to discharge the battery. Note that to check this, you really need to physically check the rocker switch: you can't see its state by looking on VRM or on the GX Device. On a MultiPlus-II, this rocker switch is at the bottom of the unit and needs to be in the I position, not on II.
 +
 +__Finally__, if all above didn't help - temporarily disable LOM to make sure that is not causing an issue. Detailes in this document: [[ve.bus:grid-codes-and-loss-of-mains-detection|]].
  
 === Q10: Why does the system refuse to discharge my battery? === === Q10: Why does the system refuse to discharge my battery? ===