Use the __Fronius Zero feed-in active__ menu item to double check that all above criteria are met. It will show **No** if the firmware requirement; | Use the __Fronius Zero feed-in active__ menu item to double check that all above criteria are met. It will show **No** if the firmware requirement; | ||
+ | |||
+ | Do not use a Fronius Smart Meter for limiting export when part of a Victron ESS System. More details about when a Fronius Smart Meter can, and can not be used is explained [[ac_coupling: | ||
=== 4.3.12 Grid setpoint === | === 4.3.12 Grid setpoint === | ||
Line 608: | Line 610: | ||
(This 0.1 V is the threshold for 12 V systems; for 24 V the threshold is 0.2 V above; and for 48 V it is 0.4V above.) | (This 0.1 V is the threshold for 12 V systems; for 24 V the threshold is 0.2 V above; and for 48 V it is 0.4V above.) | ||
- | ==== 6.5 ESS Battery Status Code Numbers ==== | + | ==== 6.5 ESS Battery Status |
In addition to the charger states (Bulk/ | In addition to the charger states (Bulk/ |