energy-meters:et112 [2020-11-03 05:11] – [Option B: Wired connection to GX device] guy_stewartenergy-meters:et112 [2021-03-20 02:51] guystewart
Line 13: Line 13:
   - Measure the output of a AC Genset   - Measure the output of a AC Genset
  
-The meter is connected to the GX device (e.g. CCGX, Cerbo GX). There are two options in its wiring:+The meter is connected to the GX device (e.g. Cerbo GX). There are two options in its wiring:
  
   - Direct connection, either using the RS485 to USB interface with 1.8m cable length, or the 5.0m cable.   - Direct connection, either using the RS485 to USB interface with 1.8m cable length, or the 5.0m cable.
Line 49: Line 49:
 ==== Option A: wireless Zigbee connection ==== ==== Option A: wireless Zigbee connection ====
 === Step 1. === === Step 1. ===
-Connect the Zigbee to USB converter to the CCGX using the supplied USB cable. A few seconds after connecting, the active LED should be on and the TX/RX LED should be blinking (the converter takes its power from the CCGX, so the GX device needs to be switched on as well).+Connect the Zigbee to USB converter to the GX device using the supplied USB cable. A few seconds after connecting, the active LED should be on and the TX/RX LED should be blinking (the converter takes its power from the GX device, so the GX device needs to be switched on as well).
  
 {{system_integration:ZigbeeCoordinator.png?200}} {{system_integration:ZigbeeCoordinator.png?200}}
Line 120: Line 120:
 ===== 3. Configuration ===== ===== 3. Configuration =====
  
-After proper connection and powering up, the meter will be visible on the CCGX in the Settings -> Energy Meters menu:+After proper connection and powering up, the meter will be visible on the GX device in the Settings -> Energy Meters menu:
  
 {{ :energy-meters:em112_settings_list.png?nolink |}} {{ :energy-meters:em112_settings_list.png?nolink |}}
Line 132: Line 132:
 ==== 4. Multiple ET112 Meters in one system ==== ==== 4. Multiple ET112 Meters in one system ====
  
-To connect multiple Energy Meters, wire each meter to a separate RS485-USB converter. Which are then each plugged into a separate USB socket on the CCGX. See NOTE 1 Below+To connect multiple Energy Meters, wire each meter to a separate RS485-USB converter. Which are then each plugged into a separate USB socket on the GX device. See NOTE 1 Below
  
 Connecting multiple ET112 meters to the same RS485-USB cable is not possible: the ET112 meter has no display and its Modbus address can therefor not be changed. Connecting multiple ET112 meters to the same RS485-USB cable is not possible: the ET112 meter has no display and its Modbus address can therefor not be changed.