User Tools

Site Tools


battery_compatibility:solar_md

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
battery_compatibility:solar_md [2019-09-23 06:22] – solar_md_portal.png change kaloyanbattery_compatibility:solar_md [2022-06-18 14:14] (current) kaloyan
Line 8: Line 8:
 == Supported models == == Supported models ==
  
-^ Model ^ SS4037^ SS4074^ SS202^  +^ Model ^ SS4037^ SS4074^ SS202^ SS4143^ SS3143^  
-| Battery | {{ :battery_compatibility:solar_md_3.7kwh.jpg?direct&200% |}} | {{ :battery_compatibility:img_6542.jpg?direct&200% |}} | {{:battery_compatibility:img_9807sqlogobox.jpg.jpg?direct&200% |}} |  +| Battery | {{ :battery_compatibility:solar_md_3.7kwh.jpg?direct&200% |}} | {{ :battery_compatibility:img_6542.jpg?direct&200% |}} | {{:battery_compatibility:img_9807sqlogobox.jpg.jpg?direct&200% |}} |  {{:battery_compatibility:ss4143.png?direct&200% |}} |  {{:battery_compatibility:ss3143-01_01_p1_render2_1_.png?direct&200% |}}| 
-|ESS | yes| yes| yes| +|ESS | yes| yes| yes| yes| yes| 
-|Grid Backup | yes| yes| yes| +|Grid Backup | yes| yes| yes| yes| yes| 
-|Off-Grid | yes| yes| yes| +|Off-Grid | yes| yes| yes| yes| yes| 
-|Module capacity | 3.7kWh| 7,4kWh| 7,4kWh| +|Module capacity | 3.7kWh| 7,4kWh| 7,4kWh| 14.3kWh| 14.3kWh
-|Module limit | 256| 256| 256| +|Module limit | 256| 256| 256| 256| 256| 
-|Max capacity | 947 kWh| 1894,4 kWh| 1894,4 kWh|+|Max capacity | 947 kWh| 1894,4 kWh| 1894,kWh| 3660.8 kWh|
 |Logger V2 | yes| yes| yes| |Logger V2 | yes| yes| yes|
  
Line 118: Line 118:
 | Multiplus 48/5000/70 | 1| 3| 2| 6| | Multiplus 48/5000/70 | 1| 3| 2| 6|
 | Quattro 48/5000/70-100/100 | 1| 3| 2| 6| | Quattro 48/5000/70-100/100 | 1| 3| 2| 6|
-| Quattro 48/8000/110-100/100 | 1| 4| 2| 6| +| Quattro 48/8000/110-100/100 | 2| 4| 2| 6| 
-| Quattro 48/10000/140- 100/100 | 1| 5| 3| 9| +| Quattro 48/10000/140- 100/100 | 2| 5| 3| 9| 
-| Quattro 48/15000/200- 100/100 | 1| 6| 4| 9|+| Quattro 48/15000/200- 100/100 | 3| 6| 4| 9|
 | EasySolar 48/3000/35-50 MPPT150/70 | 1| 3| 1| 3| | EasySolar 48/3000/35-50 MPPT150/70 | 1| 3| 1| 3|
 | EasySolar 48/5000/70-100 MPPT150/100 | 1| 3| 1| 6| | EasySolar 48/5000/70-100 MPPT150/100 | 1| 3| 1| 6|
Line 132: Line 132:
 | Multiplus 48/5000/70 | 1| 3| 2| 6| | Multiplus 48/5000/70 | 1| 3| 2| 6|
 | Quattro 48/5000/70-100/100 | 1| 3| 2| 6| | Quattro 48/5000/70-100/100 | 1| 3| 2| 6|
-| Quattro 48/8000/110-100/100 | 1| 4| 2| 6| +| Quattro 48/8000/110-100/100 | 2| 4| 2| 6| 
-| Quattro 48/10000/140- 100/100 | 1| 5| 3| 9| +| Quattro 48/10000/140- 100/100 | 2| 5| 3| 9| 
-| Quattro 48/15000/200- 100/100 | 1| 6| 4| 9|+| Quattro 48/15000/200- 100/100 | 3| 6| 4| 9|
 | EasySolar 48/3000/35-50 MPPT150/70 | 1| 3| 1| 3| | EasySolar 48/3000/35-50 MPPT150/70 | 1| 3| 1| 3|
 | EasySolar 48/5000/70-100 MPPT150/100  | 1| 3| 1| 6| | EasySolar 48/5000/70-100 MPPT150/100  | 1| 3| 1| 6|
  
 +=== Battery Modules Required – per 14.3kWh (SS4143)) ===
  
 +
 +| Phases | Single Phase| Three Phase| Single Phase| Three Phase|
 +| Inverter/Charger | Self-consumption| Self-consumption| Off-grid| Off-grid|
 +| Multiplus 48/3000/35 | 1| 1| 1| 2|
 +| Multiplus 48/5000/70 | 1| 2| 1| 3|
 +| Quattro 48/5000/70-100/100 | 1| 2| 1| 3|
 +| Quattro 48/8000/110-100/100 | 1| 3| 2| 4|
 +| Quattro 48/10000/140- 100/100 | 1| 3| 3| 4|
 +| Quattro 48/15000/200- 100/100 | 2| 5| 3| 6|
 +| EasySolar 48/3000/35-50 MPPT150/70 | 1| 1| 1| 2|
 +| EasySolar 48/5000/70-100 MPPT150/100  | 1| 2| 1| 3|
  
 ===== 3. CAN Bus Wiring ===== ===== 3. CAN Bus Wiring =====
Line 278: Line 290:
 |Battery voltage.     |48V| |Battery voltage.     |48V|
 |Absorption voltage   |54.6V| |Absorption voltage   |54.6V|
 +
 +===== 7. NEW Direct communication via BMS EX =====
 +
 +==== 7.1 Communication Cable Connection ====
 +
 +It is recommended that CAT5e cable be used. The termination resistor on the last battery should be ON, the rest should be OFF. Please use between all batteries CAN2 and CAN1 straight cable connection. For the last battery to the GX device[[battery_compatibility:can-bus_bms-cable| Type B]] cable connection is required.
 +
 +The minimum firmware version of the BMS EX should be v 178
 +
 +{{:battery_compatibility:gx_device_can.png?400|}}
 +
 +
 +==== 7.2 A Battery settings ==== 
 +Refer to the BMS of LoggerV manual to configure the CANBUS 2 interface for a Victron device. Note: After changing CANBUS 2 settings on the battery, the Victron GX device will need to be rebooted.
 +
 +
 +
 +
  
battery_compatibility/solar_md.1569212542.txt.gz · Last modified: 2019-09-23 06:22 by kaloyan