battery_compatibility:solar_md [2019-08-15 11:46] – replace Venus-device with GX device guy_stewartbattery_compatibility:solar_md [2021-11-11 15:35] – [2. Minimum Battery Sizing] alexander.joist_ibc-solar.co.za
Line 103: Line 103:
 Each battery module is 72Ah (SS4037) or 144Ah (SS4074) at 48V (51.2V nominal). Each battery module is 72Ah (SS4037) or 144Ah (SS4074) at 48V (51.2V nominal).
  
-The following charge rates are managed automatically by the SolarMD LOGGER V2 and [[venus-os:start|GX device]]. Temperature effects on charge rates should be considered in the design stage in extreem hot and cold climates.+The following charge rates are managed automatically by the SolarMD LOGGER V2 and [[venus-os:start|GX device]]. Temperature effects on charge rates should be considered in the design stage in extreme hot and cold climates.
  
 Using very large solar arrays with battery banks that are too small can exceed the limits of the batteries ability to charge and possibly lead to the LOGGER V2 triggering over-current alarms. Using very large solar arrays with battery banks that are too small can exceed the limits of the batteries ability to charge and possibly lead to the LOGGER V2 triggering over-current alarms.
Line 118: Line 118:
 | Multiplus 48/5000/70 | 1| 3| 2| 6| | Multiplus 48/5000/70 | 1| 3| 2| 6|
 | Quattro 48/5000/70-100/100 | 1| 3| 2| 6| | Quattro 48/5000/70-100/100 | 1| 3| 2| 6|
-| Quattro 48/8000/110-100/100 | 1| 4| 2| 6| +| Quattro 48/8000/110-100/100 | 2| 4| 2| 6| 
-| Quattro 48/10000/140- 100/100 | 1| 5| 3| 9| +| Quattro 48/10000/140- 100/100 | 2| 5| 3| 9| 
-| Quattro 48/15000/200- 100/100 | 1| 6| 4| 9|+| Quattro 48/15000/200- 100/100 | 3| 6| 4| 9|
 | EasySolar 48/3000/35-50 MPPT150/70 | 1| 3| 1| 3| | EasySolar 48/3000/35-50 MPPT150/70 | 1| 3| 1| 3|
 | EasySolar 48/5000/70-100 MPPT150/100 | 1| 3| 1| 6| | EasySolar 48/5000/70-100 MPPT150/100 | 1| 3| 1| 6|
Line 132: Line 132:
 | Multiplus 48/5000/70 | 1| 3| 2| 6| | Multiplus 48/5000/70 | 1| 3| 2| 6|
 | Quattro 48/5000/70-100/100 | 1| 3| 2| 6| | Quattro 48/5000/70-100/100 | 1| 3| 2| 6|
-| Quattro 48/8000/110-100/100 | 1| 4| 2| 6| +| Quattro 48/8000/110-100/100 | 2| 4| 2| 6| 
-| Quattro 48/10000/140- 100/100 | 1| 5| 3| 9| +| Quattro 48/10000/140- 100/100 | 2| 5| 3| 9| 
-| Quattro 48/15000/200- 100/100 | 1| 6| 4| 9|+| Quattro 48/15000/200- 100/100 | 3| 6| 4| 9|
 | EasySolar 48/3000/35-50 MPPT150/70 | 1| 3| 1| 3| | EasySolar 48/3000/35-50 MPPT150/70 | 1| 3| 1| 3|
 | EasySolar 48/5000/70-100 MPPT150/100  | 1| 3| 1| 6| | EasySolar 48/5000/70-100 MPPT150/100  | 1| 3| 1| 6|
  
 +=== Battery Modules Required – per 14.3kWh (SS4143)) ===
  
 +
 +| Phases | Single Phase| Three Phase| Single Phase| Three Phase|
 +| Inverter/Charger | Self-consumption| Self-consumption| Off-grid| Off-grid|
 +| Multiplus 48/3000/35 | 1| 1| 1| 2|
 +| Multiplus 48/5000/70 | 1| 2| 1| 3|
 +| Quattro 48/5000/70-100/100 | 1| 2| 1| 3|
 +| Quattro 48/8000/110-100/100 | 1| 3| 2| 4|
 +| Quattro 48/10000/140- 100/100 | 1| 3| 3| 4|
 +| Quattro 48/15000/200- 100/100 | 2| 5| 3| 6|
 +| EasySolar 48/3000/35-50 MPPT150/70 | 1| 1| 1| 2|
 +| EasySolar 48/5000/70-100 MPPT150/100  | 1| 2| 1| 3|
  
 ===== 3. CAN Bus Wiring ===== ===== 3. CAN Bus Wiring =====
Line 233: Line 245:
 ---- ----
  
-  * On the Solar MD portal ([[http://login.mypower24.co.za]]) Select Victron CAN Translator on CAN2: +  * On the Solar MD portal ([[http://login.mypower24.co.za]]) Select Victron Bridge on CAN2: 
 Menu path:  Menu path: 
  
-My Devices → Logger → Interfaces → CANBUS2 . After choosing Victron CAN Translator, proceed with Software reboot on the Logger V2 in the Tab  "System Settings"+My Devices → Logger → Interfaces → CANBUS2. After choosing Victron Bridge, proceed with Software reboot on the Logger V2 in the Tab  "System Settings"
  
 {{:battery_compatibility:solar_md_portal.png?direct |}} {{:battery_compatibility:solar_md_portal.png?direct |}}
 +
  
 ---- ----
Line 277: Line 290:
 |Battery voltage.     |48V| |Battery voltage.     |48V|
 |Absorption voltage   |54.6V| |Absorption voltage   |54.6V|
- 
  
battery_compatibility/solar_md.txt · Last modified: 2022-06-18 14:14 by kaloyan