====== Victron & Redflow ZBM ====== | ====== Victron & Redflow ZBM ====== | ||
- | http:// | + | http:// |
==== Compatible Victron products ==== | ==== Compatible Victron products ==== | ||
Line 9: | Line 9: | ||
==== Charge profile ===== | ==== Charge profile ===== | ||
- | - Charge voltage 57.6V (up to 50 Amps per battery, and current per battery self-limits if you limit the voltage) | ||
- | - Linear charge all the way from empty to full (all charge phases are the same - same ‘flat’ voltage). | ||
- | - No need for any sort of battery ‘conditioning’ cycling at all | ||
- | Charger settings: | + | See the information for the Redflow ZCell at https://www.victronenergy.com/ |
- | - Set both absorption and float voltage to 57.6V | + | |
- | - disable storage mode. | + | |
- | - disable bulk protection(?? | + | |
- | - using Assistants, such as the Hub-4 Assistant, is possible but not required. | + | |
===== Color Control GX ===== | ===== Color Control GX ===== | ||
- | The Color Control GX has built in support for the Redflow ZBM battery and its Modbus protocol. | + | Redflow ZBM batteries can be directly interfaced to the CCGX for monitoring and control (see below). |
+ | |||
+ | Alternatively one or more ZBM batteries can be used with the Redflow/ | ||
+ | |||
+ | For the direct-attach option, the Color Control GX has built in support for directly attaching to one or more Redflow ZBM batteries using the built in Modbus | ||
{{ : | {{ : | ||
Line 29: | Line 27: | ||
- Control the battery: set it to run mode, initiate a maintenance cycle, clear the alarms and more. | - Control the battery: set it to run mode, initiate a maintenance cycle, clear the alarms and more. | ||
- Configure the battery: the CCGX will automatically assign a unique Modbus address to each battery. Just make sure to connect them, slowly, one by one. After connecting one, wait for it to show up on the CCGX, and then connect the next one. Additionally, | - Configure the battery: the CCGX will automatically assign a unique Modbus address to each battery. Just make sure to connect them, slowly, one by one. After connecting one, wait for it to show up on the CCGX, and then connect the next one. Additionally, | ||
- | |||