battery_compatibility:pylontech_phantom [2019-08-22 11:16] – changed inverter parameter low voltage settings boekelbattery_compatibility:pylontech_phantom [2019-10-26 12:55] boekel
Line 118: Line 118:
 === Charger tab === === Charger tab ===
 ^ Parameter              ^ Setting ^ ^ Parameter              ^ Setting ^
-| Battery type           | Lithium |+| Battery type           | Lithium | 
 | Charge curve           | Fixed    | Charge curve           | Fixed   
-| Absorption voltage     53.V  | +| Absorption voltage     52.V  | 
-| Float voltage          | 53.0 V  | +| Float voltage          | 51.0 V  | 
 | Absorption time        | 1 Hr    | | Absorption time        | 1 Hr    |
  
-Note: make sure to double check the float voltage after completing Assistants, and if necessary set it back to 53.0 V.+Note: make sure to double check the float voltage after completing Assistants, and if necessary set it back to 51.0 V
 + 
 +Note For off-grid use: ignore the 'bms assistant required' warning.
  
 === 4.3 Inverter Settings === === 4.3 Inverter Settings ===