battery_compatibility:pylontech_phantom
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revisionNext revision | Previous revisionNext revisionBoth sides next revision | ||
battery_compatibility:pylontech_phantom [2019-02-18 22:06] – guystewart | battery_compatibility:pylontech_phantom [2019-05-06 11:28] – [3. CAN-bus Wiring] guystewart | ||
---|---|---|---|
Line 88: | Line 88: | ||
The batteries will automatically detect and link to each other, no adjustment of dip switches or software changes are necessary on the batteries. | The batteries will automatically detect and link to each other, no adjustment of dip switches or software changes are necessary on the batteries. | ||
- | The battery with the empty link port 0 is the master battery. | + | The battery with the empty link port 0 is the master battery. |
+ | You must use the //VE.Can to CAN-bus BMS type B Cable//, part number ASS030720018, | ||
+ | |||
+ | Plug the type B cable with the side which is labeled Battery BMS into the Pylontech CAN port of the master battery. Plug the side labeled Victron VE.Can into the [[venus-os: | ||
Then, plug a [[https:// | Then, plug a [[https:// | ||
Line 227: | Line 230: | ||
The Pylontech manual contains additional diagnostic and troubleshooting information, | The Pylontech manual contains additional diagnostic and troubleshooting information, | ||
- | ===== 9. FAQ ===== | ||
- | **The maximum charge and discharge current is limited to 25A, but the data sheet tells me the maximum is 100A.** | + | ===== 9. FAQ and Known Issues===== |
+ | |||
+ | ==== The maximum charge and discharge current is limited to 25A, but the data sheet tells me the maximum is 100A. ==== | ||
The maximum current is limited to keep the battery healthy and reach the 10 year guarantee. In off-grid, the inverter can draw more than the 25A limit to run the loads, make sure you have sufficient batteries installed to keep the load per battery around this limit. | The maximum current is limited to keep the battery healthy and reach the 10 year guarantee. In off-grid, the inverter can draw more than the 25A limit to run the loads, make sure you have sufficient batteries installed to keep the load per battery around this limit. | ||
- | **After charging the battery the charge current often changes between 0A and 25A.** | + | ==== After charging the battery the charge current often changes between 0A and 25A. ==== |
This is caused by cell balancing inside the battery. This happens with new batteries and after a deep discharge. | This is caused by cell balancing inside the battery. This happens with new batteries and after a deep discharge. | ||
+ | ==== My system isn't charging at the rated capacity, or my PV is shutting down ==== | ||
+ | Pylontech' | ||
+ | |||
+ | You can confirm if this is affecting your installation be entering the Pylontech Battery menu on your Venus-device, | ||
===== 10. Further Information ===== | ===== 10. Further Information ===== | ||
Line 248: | Line 257: | ||
===== DISQUS ===== | ===== DISQUS ===== | ||
~~DISQUS~~ | ~~DISQUS~~ | ||
- |
battery_compatibility/pylontech_phantom.txt · Last modified: 2023-11-13 14:41 by guy_stewart