battery_compatibility:lg_chem_resu [2018-06-11 09:51] guystewartbattery_compatibility:lg_chem_resu [2018-12-06 14:07] – Venus-device links guy_stewart
Line 7: Line 7:
 === A Venus device is required (either Color Control GX (CCGX) or the VENUS GX) ===  === A Venus device is required (either Color Control GX (CCGX) or the VENUS GX) === 
  
-It is essential to use the CAN-bus connection of the CCGX or VENUS GX with the LG batteries for the keep-alive signal, communication of charge and discharge limits, error codes and state of charge. +It is essential to use the CAN-bus connection of the [[venus-os:start|Venus-device]] with the LG batteries for the keep-alive signal, communication of charge and discharge limits, error codes and state of charge. 
  
 The minimum required firmware version for the [[https://www.victronenergy.com/panel-systems-remote-monitoring/color-control|Color Control GX]] is v2.15. It is highly recommended to use the latest firmware version on all connected devices, including CCGX/VENUS GX, Inverter/Charger and MPPTs. There are regular updates to improve performance and reliability.  The minimum required firmware version for the [[https://www.victronenergy.com/panel-systems-remote-monitoring/color-control|Color Control GX]] is v2.15. It is highly recommended to use the latest firmware version on all connected devices, including CCGX/VENUS GX, Inverter/Charger and MPPTs. There are regular updates to improve performance and reliability. 
Line 23: Line 23:
  
 ==== Color Control GX or Venus GX required ==== ==== Color Control GX or Venus GX required ====
-To use the LG Chem Resu and Victron equipment, it is necessary to use a CCGX or VenusGX. It takes care of sending the necessary canbus keep-a-live message to the LG Resu. Without it, the LG Resu will open its internal circuitbreaker after 10 minutes.+To use the LG Chem Resu and Victron equipment, it is necessary to use a [[venus-os:start|Venus-device]] (eg CCGX or VenusGX). It takes care of sending the necessary canbus keep-a-live message to the LG Resu. Without it, the LG Resu will open its internal circuitbreaker after 10 minutes.
  
-Do not attempt firmware updates using the LG Chem battery for power until you can confirm that the battery is connected and showing on the Venus device.+Do not attempt firmware updates using the LG Chem battery for power until you can confirm that the battery is connected and showing on the [[venus-os:start|Venus-device]].
  
 ==== Wiring of communication cables ==== ==== Wiring of communication cables ====
-Use the //VE.Can to CAN-bus BMS type B Cable//, part number ASS030720018. Plug the side which is labeled Battery BMS into the LG Chem Resu BMS. Plug the side labeled Victron VE.Can into the Venus-device.+Use the //VE.Can to CAN-bus BMS type B Cable//, part number ASS030720018. Plug the side which is labeled Battery BMS into the LG Chem Resu BMS. Plug the side labeled Victron VE.Can into the [[venus-os:start|Venus-device]].
  
 Then, plug a [[https://www.victronenergy.com/accessories/ve-can-rj45-terminator|VE.Can terminator]] in the other VE.Can socket on the CCGX. Two VE.Can terminators are included with the package of the CCGX as an accessory, only one is used. Keep the other one as a spare. Then, plug a [[https://www.victronenergy.com/accessories/ve-can-rj45-terminator|VE.Can terminator]] in the other VE.Can socket on the CCGX. Two VE.Can terminators are included with the package of the CCGX as an accessory, only one is used. Keep the other one as a spare.