 Adjust the maximum current on the MPPT's to ensure that the combined total charge power cannot exceed the maximum rated charge current for the LiTE or LiTE's in the system.  Adjust the maximum current on the MPPT's to ensure that the combined total charge power cannot exceed the maximum rated charge current for the LiTE or LiTE's in the system. 
  
-===== Large Parallel Banks (>3000A Current Limits) =====+===== Large Parallel Banks (>6500A Current Limits) =====
  
-The CAN Bus hexadecimal message format that the Victron GX controller uses cannot accept a number larger than 3000 for the Charge Current Limit (CCL) and the Discharge Current Limit (DCL). +The CAN Bus hexadecimal message format that the Victron GX controller uses cannot accept a number larger than 6500 for the Charge Current Limit (CCL) and the Discharge Current Limit (DCL). 
  
-Freedom Won LiTE batteries are designed for very high current capabilities, which means that it is not uncommon for a system to exceed this 3000A limit if there are multiple Freedom Won LiTE batteries connected in parallel. +Freedom Won LiTE batteries are designed for very high current capabilities, which means that it is not uncommon for a system to exceed this 6500A limit if there are multiple Freedom Won LiTE batteries connected in parallel. 
  
-The designer must refer to the LiTE specification sheet to determine if the total of the CCL or DCL for all the batteries connected on the system will add up to a value greater than 3000A+The designer must refer to the LiTE specification sheet to determine if the total of the CCL or DCL for all the batteries connected on the system will add up to a value greater than 6500A
  
-If this is the case, the commissioning technician must arrange with Freedom Won technical support ([[support@freedomwon.co.za]]) to reduce these limits so that the total falls at or under 3000A. This is achieved simply and quickly by the Freedom Won support team installing a custom profile into the battery via a remote desktop session using a computer connected to the master battery.+If this is the case, the commissioning technician must arrange with Freedom Won technical support ([[support@freedomwon.co.za]]) to reduce these limits so that the total falls at or under 6500A. This is achieved simply and quickly by the Freedom Won support team installing a custom profile into the battery via a remote desktop session using a computer connected to the master battery.
  
 Please refer to the note below regarding scheduling time with support if required. Please refer to the note below regarding scheduling time with support if required.