battery_compatibility:byd_b-box
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
battery_compatibility:byd_b-box [2020-02-11 13:05] – [5. GX device Configuration] guy_stewart | battery_compatibility:byd_b-box [2024-01-22 07:32] (current) – guy_stewart | ||
---|---|---|---|
Line 1: | Line 1: | ||
- | ====== Victron & BYD B-Box ===== | + | ====== Victron & BYD ====== |
- | + | ||
- | The combination of Victron products with BYD Battery-Box LV lithium batteries has been tested and certified by the Victron and BYD R&D departments. This combination has extensive field experience and is actively supported by both companies. | + | ^ Battery ^ Pro 2.5-10.0 ^ Pro 12.8 & 13.8 ^ L 3.5-14.0 |
- | + | | Appearance | {{ : | |
- | The BYD B-Box includes an integrated Battery Management System (BMS) with each battery cell module, and a Battery Management Unit (BMU) that interfaces with the Victron [[venus-os: | + | | ESS | yes| yes| yes| yes| yes| yes| |
- | + | | Grid Backup| | |
- | + | | Off-Grid| | |
- | + | | Module capacity| | |
- | ^ Battery ^ Pro 2.5-10.0 ^ Pro 12.8 & 13.8 ^ L 3.5-14.0 ^ | + | | Module limit | 32| 32| 12| 64| 64| 64| |
- | | Appearance | {{ : | + | | Max capacity| |
- | | ESS | yes| yes| yes| | + | |
- | | Grid Backup| | + | |
- | | Off-Grid| | + | |
- | | Module capacity| | + | |
- | | Module limit | 32| 32| 12| | + | |
- | | Max capacity| | + | |
- | + | ||
- | + | ||
===== 1. Product & System compatibility ===== | ===== 1. Product & System compatibility ===== | ||
- | === 1.1 Offgrid, Backup and Energy Storage Systems | + | === 1.1 Offgrid, Backup and Energy Storage Systems |
Victron + BYD B-Box can be used for the following system types: | Victron + BYD B-Box can be used for the following system types: | ||
Line 27: | Line 18: | ||
* Off-grid | * Off-grid | ||
+ | __Special note for Off-Grid systems__ | ||
+ | For Off-grid systems, its strongly recommend to make sure there is a minimum of DC-Coupled PV (= MPPT Solar Charger) in the system. Ie. not only AC-Coupled PV. Also, minimum battery configuration, | ||
- | === 1.2 A GX device is required, eg Color Control | + | === 1.2 A GX device is required, eg Cerbo GX, etc === |
- | It is essential to use the CAN-bus connection of a [[venus-os: | + | It is essential to use the BMS-Can (or CAN-bus) connection of a [[venus-os: |
- | When used with B-Box batteries, the minimum supported firmware version for the [[venus-os: | + | When used with B-Box Pro series |
- | === 1.3 All 48V Multis, MultiPlusses, | + | === 1.3 All 48V Multis, MultiPlusses, |
The minimum supported firmware version is 469. Updating to the latest firmware is recommended for new installations, | The minimum supported firmware version is 469. Updating to the latest firmware is recommended for new installations, | ||
Line 45: | Line 38: | ||
In off-grid systems, the control functions of the BYD Battery Management System (BMS) are built into the latest version of the [[venus-os: | In off-grid systems, the control functions of the BYD Battery Management System (BMS) are built into the latest version of the [[venus-os: | ||
+ | === 1.4 Solar Charger compatibility === | ||
+ | All 48V BlueSolar and SmartSolar VE.Direct MPPT Chargers are compatible (*). | ||
+ | Some of our Solar Chargers feature a VE.Direct communication port, some feature a VE.Can communication port, and some feature both. Both of these types of communication ports can be used to connect the Solar charger to the GX Device. Such connection is mandatory, because it is used to regulate charge currents and voltages. | ||
- | === 1.4 All 48V BlueSolar and SmartSolar MPPT Chargers are compatible === | + | When planning |
- | + | ||
- | For proper operation, the B-Box battery needs to be able to control the charge current of the solar MPPTs. | + | |
- | It is recommended | + | |
- | + | ||
- | __MPPTs with a VE.Direct port__ | + | |
- | + | ||
- | MPPTs are controlled via the [[venus-os: | + | |
- | + | ||
- | The MPPT requires connection to the [[venus-os: | + | |
- | To test operation, try disconnecting the [[venus-os:start|GX device]] from the MPPT. After a time-out, the MPPT will stop charging and flash an error code on its LEDs. The error code is [[https:// | + | |
- | + | ||
- | __MPPTs with a VE.Can port and VE.Direct port__ | + | |
- | + | ||
- | Firmware should be at least version 1.04. | + | |
- | + | ||
- | When using VE.Can MPPT' | + | |
- | Please note that older model VE.Can MPPTs (without VE.direct and with built in screen) are no longer supported | + | (*) with exception of the models “BlueSolar MPPT 150/70 CAN-bus” and “BlueSolar MPPT 150/85 CAN-bus” which are end-of-life since 2019. Legacy systems, historically installed |
=== 1.5 Battery compatibility === | === 1.5 Battery compatibility === | ||
Line 78: | Line 58: | ||
| B-BOX Compact | | B-BOX Compact | ||
| B-BOX L 3.5-14.0 | | B-BOX L 3.5-14.0 | ||
+ | | B-BOX Premium LVL 15.4 | | ||
+ | | B-BOX Premium LVS 4.0 | | ||
+ | | B-BOX LV Flex 5.0 | | ||
- | BYD also releases firmware update for their BMU and BMS. BMU Firmware versions earlier than V4-13 are not compatible with Victron equipment and can cause the battery to not be detected. | + | BYD also releases firmware update for their BMU and BMS. |
- | Minimum BYD firmware version: BMU_V2_V4-13_15-Mar-2017. | + | B-Box Pro BMU Firmware versions earlier than V4-13 are not compatible with Victron equipment and can cause the battery to not be detected. |
- | On-screen, or via Remote Console on the [[venus-os: | + | Minimum BYD firmware version for B-Box Pro: BMU_V2_V4-13_15-Mar-2017. |
- | + | ||
- | Batteries with older firmware versions can be updated. Please contact BYD for more information. | + | |
+ | BYD B-Box Premium batteries firmware should be no less than V1.4, and the BMS firmware should be no less than V1.3. If necessary, this can be updated automatically via the ethernet port on the BMU when connected to the internet. | ||
+ | Victron is not compatible with the BYD HVS/HVM range of high-voltage batteries. | ||
===== 2. Minimum Battery Sizing ===== | ===== 2. Minimum Battery Sizing ===== | ||
The following information is provided by BYD, it is reproduced here for your convenience and should always be confirmed with the latest BYD manuals and specifications. | The following information is provided by BYD, it is reproduced here for your convenience and should always be confirmed with the latest BYD manuals and specifications. | ||
- | Each battery | + | Each B-Box Pro 2.5 battery |
The following charge rates are managed automatically by the BYD BMU and [[venus-os: | The following charge rates are managed automatically by the BYD BMU and [[venus-os: | ||
Line 102: | Line 85: | ||
=== Battery Modules Required - Pro 2.5 === | === Battery Modules Required - Pro 2.5 === | ||
- | |||
|Phases| | |Phases| | ||
| Inverter/ | | Inverter/ | ||
- | | | + | | |
- | | | + | | |
+ | | Inverter RS & Multi RS 48/ | ||
| Quattro 48/ | | Quattro 48/ | ||
| Quattro 48/ | | Quattro 48/ | ||
- | | Quattro 48/ | + | | Quattro |
- | | Quattro 48/ | + | | Quattro |
- | | EasySolar 48/ | + | | EasySolar |
- | | EasySolar 48/ | + | | EasySolar 48/ |
Line 120: | Line 103: | ||
|Phases| | |Phases| | ||
| Inverter/ | | Inverter/ | ||
- | | | + | | |
- | | | + | | |
+ | | Inverter RS & Multi RS 48/ | ||
| Quattro 48/ | | Quattro 48/ | ||
| Quattro 48/ | | Quattro 48/ | ||
- | | Quattro 48/ | + | | Quattro |
- | | Quattro 48/ | + | | Quattro |
- | | EasySolar 48/ | + | | EasySolar |
| EasySolar 48/ | | EasySolar 48/ | ||
Line 133: | Line 117: | ||
|Phases| | |Phases| | ||
| Inverter/ | | Inverter/ | ||
- | | | + | | |
- | | | + | | |
+ | | Inverter RS & Multi RS 48/ | ||
| Quattro 48/ | | Quattro 48/ | ||
| Quattro 48/ | | Quattro 48/ | ||
- | | Quattro 48/ | + | | Quattro |
- | | Quattro 48/ | + | | Quattro |
- | | EasySolar 48/ | + | | EasySolar |
| EasySolar 48/ | | EasySolar 48/ | ||
Line 147: | Line 132: | ||
+ | === Battery Modules Required - Premium LVL 15.4 === | ||
+ | |Phases| | ||
+ | | Inverter/ | ||
+ | | MultiPlus & MultiPlus II & MP-II GX 48/ | ||
+ | | MultiPlus, MultiPlus II, MP-II GX, & Quattro-II 48/ | ||
+ | | Inverter RS & Multi RS 48/ | ||
+ | | Quattro 48/ | ||
+ | | Quattro 48/ | ||
+ | | Quattro & MultiPlus-II 48/ | ||
+ | | Quattro & MultiPlus-II 48/ | ||
+ | | EasySolar & EasySolar-II 48/ | ||
+ | | EasySolar 48/ | ||
- | The specification for these minimum battery sizes was obtained from [[http:// | ||
+ | === Battery Modules Required - Premium LVS 4.0 === | ||
+ | |Phases| | ||
+ | | Inverter/ | ||
+ | | MultiPlus & MultiPlus II & MP-II GX 48/ | ||
+ | | MultiPlus, MultiPlus II, MP-II GX, & Quattro-II 48/ | ||
+ | | Inverter RS & Multi RS 48/ | ||
+ | | | ||
+ | | Quattro 48/ | ||
+ | | Quattro & MultiPlus-II 48/ | ||
+ | | Quattro & MultiPlus-II 48/ | ||
+ | | | ||
+ | | | ||
+ | * Note for 7 units two stacks are required. One stack is 4 battery modules, the other is 3. | ||
- | ===== 3. CANBus Wiring ===== | + | === Battery Modules Required - Premium LV Flex 5.0 === |
- | Use the //VE.Can to CAN-bus BMS type A Cable//, part number ASS030710018. Plug the side which is labeled Battery BMS into the BYD BMS. Plug the side labeled Victron VE.Can into the [[venus-os:start|GX device]]. | + | |Phases| |
+ | | Inverter/Charger | On-Grid | On-Grid | Off-grid | Off-grid | | ||
+ | | MultiPlus 48/500 & 48/ | ||
+ | | MultiPlus 48/1200 & 48/ | ||
+ | | MultiPlus 48/ | ||
+ | | MultiPlus & MultiPlus II & MP-II GX 48/3000/35| 1| 3| 2| 4| | ||
+ | | MultiPlus, MultiPlus II, MP-II GX, & Quattro-II 48/ | ||
+ | | Inverter RS & Multi RS 48/ | ||
+ | | | ||
+ | | Quattro 48/ | ||
+ | | Quattro & MultiPlus-II 48/ | ||
+ | | Quattro & MultiPlus-II 48/ | ||
+ | | | ||
+ | | | ||
- | Then, plug a [[https:// | ||
- | More information about the cable can be found in [[battery_compatibility: | + | **" |
- | Without properly connecting this cable, the battery | + | The specification for these minimum |
- | It is important to ensure this connection and display of the battery on the [[venus-os:start|GX device]] display before attempting firmware updates or settings changes on other devices if they depend on the power supply from the battery. Without this connection, the battery may turn off unexpectedly. If a reliable DC power supply is required, you can temporarily disconnect the individual BYD battery cells inside their cabinet from the internal Battery Management Unit (BMU). It is the BMU that signals the battery cells to shut down if the signal from the [[venus-os: | + | ===== 3. CAN-Bus wiring between |
+ | Use the //VE.Can to CAN-bus BMS type A Cable//, part number ASS030710018. Plug the side which is labeled Battery BMS into the BYD BMS. Plug the side labeled Victron VE.Can into the [[venus-os: | ||
+ | Then, plug a [[https:// | ||
+ | More information about the cable can be found in [[battery_compatibility: | ||
- | === 3.1 Wiring of the Allow-to-charge and allow-to-discharge contacts === | + | Without properly connecting this cable, |
- | + | ||
- | Using the latest firmware | + | |
- | If you have an existing system that is configured using the Allow-to-charge contacts, and it is operating correctly, you do not need to make any changes. | + | |
- | + | ||
- | The MPPTs with a VE.Can port have a dedicated Remote On/Off input. It needs to be connected to battery | + | |
- | + | ||
- | B-Box relays: | + | |
- | + | ||
- | * Relay T1-T2: closed if allowed to discharge | + | |
- | * Relay T4-T5: closed if allowed to charge | + | |
- | + | ||
- | {{: | + | |
+ | It is important to ensure this connection and display of the battery on the [[venus-os: | ||
===== 4. VEConfigure settings ===== | ===== 4. VEConfigure settings ===== | ||
Line 203: | Line 216: | ||
| Charge curve | Fixed | | Charge curve | Fixed | ||
| Absorption voltage | | Absorption voltage | ||
- | | Float voltage | + | | Absorption voltage off-grid systems |
+ | | Float voltage | ||
| Absorption time | 1 Hr | | | Absorption time | 1 Hr | | ||
- | Note: make sure to double check the float voltage after completing Assistants, and if necessary set it back to 55 V. | + | Notes: |
+ | |||
+ | - make sure to double check the float voltage after completing Assistants, and if necessary set it back to 55 V. | ||
+ | - Setting the Absorption voltage for off-grid systems to 56.5V is to ensure the PV Inverter Assistant works properly. Setting this voltage to 56.5V, ie a bit higher than the default 55.2V, prevents the Frequency shift algorithm to lock at 52.7 or 53 Hz, and thereby disabling AC-Coupled PV Inverters. The setting has no effect on the actual charge voltage as used by the inverter and other components in the system, since these are directed directly by the battery via DVCC. | ||
=== 4.3 Inverter Settings === | === 4.3 Inverter Settings === | ||
Line 237: | Line 254: | ||
- | ===== 5. GX device | + | ===== 5. GX device |
On the [[venus-os: | On the [[venus-os: | ||
Line 245: | Line 262: | ||
|Shared Voltage Sense |OFF| | |Shared Voltage Sense |OFF| | ||
- | If you have a VE.Can MPPT, it is advised to use the Venus GX in place of the CCGX. | ||
- | * Select the //CAN-bus BMS (500 kbit/s)// CAN-profile in the CCGX. Menu path: //Settings -> Services -> CAN-profile// | + | * Select the //CAN-bus BMS (500 kbit/s)// CAN-profile in the GX device. Menu path: //Settings -> Services -> CAN-profile// |
* After properly wiring and setting up, the B-Box will be visible as a battery in the device list: | * After properly wiring and setting up, the B-Box will be visible as a battery in the device list: | ||
Line 258: | Line 274: | ||
Note these limits have been adjusted higher by BYD during firmware updates, so the charge and discharge current limit figure may appear slightly higher. | Note these limits have been adjusted higher by BYD during firmware updates, so the charge and discharge current limit figure may appear slightly higher. | ||
- | |||
- | === Color Control GX Configuration === | ||
- | | ||
- | The CCGX only has one available VE.Can port. It is not possible to connect both CAN products such as VE.Can MPPT (250 kbit/s) and an B-Box battery CAN-bus (500 kbit/s) together on the CCGX. As the BYD Battery MUST be connected, you will need to use the port for that. This will mean no data is collected from the VE.Can MPPT, nor can the CCGX control it. This means you are required to use the "Allow to Charge" | ||
=== GX Device with multiple CAN-bus port configuration === | === GX Device with multiple CAN-bus port configuration === | ||
Line 271: | Line 283: | ||
The CAN-bus connections are galvanically isolated at the BYD BMU. There is no issues using the non-isolated connection of the VGX. | The CAN-bus connections are galvanically isolated at the BYD BMU. There is no issues using the non-isolated connection of the VGX. | ||
- | ===== 6. VE-Direct | + | === Color Control GX Configuration - Not Recommended |
+ | |||
+ | The CCGX only has one available VE.Can interface. It is not possible to connect both CAN products such as VE.Can MPPT (250 kbit/s) and an B-Box battery BMS-Can CAN-bus (500 kbit/s) together on the CCGX. As the BYD Battery MUST be connected, you will need to use the port for that. This will mean no data is collected from the VE.Can | ||
- | In normal operation | + | For this reason it is recommended to use the Cerbo GX instead. |
- | This section presumes familiarity with [[victronconnect: | + | ===== 6. Solar Charging ===== |
- | The settings below are a precautionary measure. | + | ==== 6.1 Victron MPPT charger settings ==== |
- | ^MPPT Parameter ^ Setting ^ | + | Victron MPPT charge characteristics are automatically configured & governed by the [[venus-os: |
- | |Battery voltage. |48V| | + | |
+ | ^ MPPT Parameter ^ Setting ^ | ||
+ | |Battery voltage | ||
|Absorption voltage | |Absorption voltage | ||
+ | Use [[victronconnect: | ||
+ | |||
+ | ==== 6.2 Self-Startup from Low voltage shutdown modes ==== | ||
+ | |||
+ | In a correctly configured system, the inverter will shut itself down before the batteries enter a self protective shut down state. | ||
+ | |||
+ | Therefore it is essential that there is also either a generator or DC MPPT charge controller for overall system stability. If your system is charged only with an AC-coupled PV inverter, this may prevent the AC-coupled PV inverter from starting up to recharge the batteries. | ||
+ | |||
+ | Even a single 100/20 48V MPPT charger unit with 2 x 60 cell solar panels would be sufficient to add this self correcting mechanism able to maintain the DC bus voltage and improve longterm system reliability considerably from accidental deep discharge and subsequent shut down. | ||
===== 7. Example Wiring Diagram ===== | ===== 7. Example Wiring Diagram ===== | ||
Line 293: | Line 318: | ||
=== Step 0. If the Inverter/ | === Step 0. If the Inverter/ | ||
- | As a safety precaution, the inverter/ | + | When the grid is connected there are two software controls to sustain voltage. The Minimum SOC (while grid is connected) set in the GX device, and the sustain voltage (set in the ESS assistant). |
+ | |||
+ | If the grid fails and no AC supply is available, in this deeply discharged state, and the battery has set the Discharge Current Limit (DCL) to 0A, then the inverter will turn off in a software off state. | ||
+ | |||
+ | The GX device | ||
+ | Note in this state an AC PV inverter will not produce any power, and will not start up, as it requires the inverter to create the sine wave to synchronise. | ||
+ | |||
+ | If the AC grid or generator, or DC MPPT is connected, then the battery will begin to charge and then the inverter will start itself again automatically, | ||
+ | If instead | ||
+ | |||
+ | If you then reconnect a DC charge source, or AC input supply (grid or generator), after approximately 2 minutes | ||
- | You can then start the inverter/ | ||
=== Step 1. Check that the BYD battery is visible on the GX device list === | === Step 1. Check that the BYD battery is visible on the GX device list === | ||
Line 348: | Line 382: | ||
* Could be a temporary issue, that corrects self automatically after a short while (matter of minutes). | * Could be a temporary issue, that corrects self automatically after a short while (matter of minutes). | ||
* Could be an external issue, unacceptable voltage or current. | * Could be an external issue, unacceptable voltage or current. | ||
+ | |||
===== 9. Step by Step Installation Guide ===== | ===== 9. Step by Step Installation Guide ===== | ||
There is a step by step installation video that demonstrates the essential connections and programming that is required for installation of a BYD battery in a Victron system. It is accessible via the [[https:// | There is a step by step installation video that demonstrates the essential connections and programming that is required for installation of a BYD battery in a Victron system. It is accessible via the [[https:// | ||
- | |||
- | |||
[[https:// | [[https:// | ||
Line 358: | Line 391: | ||
This written manual should be assumed to be the more accurate and up-to-date, if there are any discrepancies between the video and the written manual, | This written manual should be assumed to be the more accurate and up-to-date, if there are any discrepancies between the video and the written manual, | ||
- | A user contributed [[battery_compatibility: | + | ==== Introduction to the new BYD Premium range LVL and LVS ==== |
- | ===== 10. Known Issues ===== | + | |
+ | [[https:// | ||
+ | |||
+ | ==== Introduction to the new BYD Flex 5.0 ==== | ||
+ | |||
+ | BYD recorded a webinar introducing their Flex 5.0 battery - it is available to watch here - https:// | ||
+ | |||
+ | Victron presented more information that was specific to our integration as part of that webinar - available here - https:// | ||
+ | |||
+ | ==== User contributed installation guide ==== | ||
+ | |||
+ | A user contributed [[battery_compatibility: | ||
+ | |||
+ | ===== 10. Known Issues | ||
+ | |||
+ | The following information only applies to the B-Box Pro models, and not to the B-Box Premium models. | ||
- | === 10.1 Inaccurate State of Charge (SoC) Readings === | + | === 10.1 Inaccurate State of Charge (SoC) Readings |
Each BYD battery module has it’s own BMS. This BMS reports it’s battery information to the BMU which is connected to the [[venus-os: | Each BYD battery module has it’s own BMS. This BMS reports it’s battery information to the BMU which is connected to the [[venus-os: | ||
Line 418: | Line 466: | ||
There has been a firmware revision for the BYD battery modules and BMU that improves cold weather performance slightly. This manual will be updated with the new (slightly improved) specifications when stock supplied with the new firmware has had sufficient time to enter the market. Contact your BYD distributor for further information about this. | There has been a firmware revision for the BYD battery modules and BMU that improves cold weather performance slightly. This manual will be updated with the new (slightly improved) specifications when stock supplied with the new firmware has had sufficient time to enter the market. Contact your BYD distributor for further information about this. | ||
- | === 10.4 Self-Startup from Low voltage shutdown modes === | ||
- | In a correctly configured | + | ===== 11. Legacy systems using allow-to-charge and allow-to-discharge contacts ===== |
+ | |||
+ | For proper operation, the B-Box battery needs to be able to control the charge current of the solar MPPTs. Which for all modern models is arranged via the VE.Can and VE.Direct digital communication protocols. The very first two BlueSolar Chargers made by Victron, the “BlueSolar MPPT 150/70 CAN-bus” and “BlueSolar MPPT 150/85 CAN-bus” models, do no support such control, and were therefor controlled with a wire: the allow-to-charge wire. | ||
+ | |||
+ | The purpose of this chapter is to serve as reference guide for legacy systems using those two solar charger models. If you have an existing | ||
+ | |||
+ | Note that these charges cannot be used with the BYD Premium LV batteries, since they do not feature the required free contacts. | ||
+ | |||
+ | === Legacy system wiring details === | ||
+ | |||
+ | The Remote On/Off input of the two mentioned solar charger models is used to signal that they can or cannot charge the battery. It needs to be connected to battery positive to enable the charger. Leaving | ||
+ | |||
+ | B-Box relays: | ||
+ | |||
+ | * Relay T1-T2: closed if allowed to discharge | ||
+ | * Relay T4-T5: closed if allowed to charge | ||
+ | |||
+ | Picture showing these connections on the BYD B-Box battery: | ||
+ | |||
+ | {{: | ||
+ | |||
+ | ===== 12. High voltage warning or alarm shown on battery status ===== | ||
+ | |||
+ | The 'high voltage' | ||
+ | |||
+ | It is easiest to confirm this diagnosis in VRM in the Advanced Widget for the Battery Monitor as it logs this data over time. | ||
+ | {{: | ||
+ | |||
+ | It is also possible to see an instantaneous cell max/min on the GX device in the Menu -> BYD Battery -> Details | ||
+ | |||
+ | |||
+ | In a normal well balanced battery installation, | ||
+ | |||
+ | {{: | ||
+ | |||
+ | In an imbalanced battery installation, | ||
+ | |||
+ | {{: | ||
+ | |||
+ | To help the batteries balance quickly, keep the batteries fully charged and the system voltage stable until the errors go away. In an ESS system, set it to 'keep batteries charged', | ||
+ | |||
+ | If you are unable to maintain the target voltage to balance the batteries without the 'high voltage' | ||
+ | |||
+ | {{: | ||
+ | |||
+ | Another method that may also help is limiting the maximum charge current that is provided by the solar chargers. In some cases this can allow a better charge without needing to reduce the overall battery charge voltage as much (or at all), by reducing the high current spikes. Charge current limits can be applied at a system level in DVCC - however they will be much more effective and quicker to react to changing conditions if applied at an individual unit level within the MPPT settings in VictronConnect: | ||
+ | |||
+ | {{: | ||
+ | |||
+ | Start with a severe current limit (i.e 50%) and then see if that resolves the issue (while still making sure the system receives a full charge). If the issue is still not resolved, continue to restrict further. | ||
+ | Once the alarms stop, then increase Max Charge Current back to the point where the issue reappears, and then reduce it again by 10%. Note this may also be seasonally affected (if solar window is limited with the changing sun angle). | ||
+ | |||
+ | All of these values can be monitored, and the settings adjustments can be performed remotely with an internet connected system via VRM and VictronConnect Remote. | ||
+ | |||
+ | If it is not possible to raise the voltage or current limits over time, and eventually disable the manual overrides without the alarms reoccurring; | ||
- | If your system | + | 1: If you have 2 or more batteries in your system, |
- | Even a single 100/20 48V MPPT charger unit with 2 x 60 cell solar panels would be sufficient to add this self correcting mechanism able to maintain the DC bus voltage and improve longterm system reliability considerably from accidental deep discharge and subsequent shut down. | + | 2: Contact your BYD dealer for further assistance (they can provide additional software to see even more detailed individual |
- | ===== 11. Further Information ===== | + | ===== 13. Further Information ===== |
For information about where to buy or find suitably qualified installers, visit the [[https:// | For information about where to buy or find suitably qualified installers, visit the [[https:// |
battery_compatibility/byd_b-box.1581422729.txt.gz · Last modified: 2020-02-11 13:05 by guy_stewart