Both sides previous revisionPrevious revisionNext revision | Previous revisionNext revisionBoth sides next revision |
battery_compatibility:byd_b-box [2020-12-08 11:45] – mvader | battery_compatibility:byd_b-box [2021-02-19 08:33] – [2. Minimum Battery Sizing] guystewart |
---|
|Phases| Single Phase| Three Phase| Single Phase| Three Phase| | |Phases| Single Phase| Three Phase| Single Phase| Three Phase| |
| Inverter/Charger | Self-consumption | Self-consumption | Off-grid | Off-grid | | | Inverter/Charger | Self-consumption | Self-consumption | Off-grid | Off-grid | |
| Multiplus 48/3000/35| 1| 3| 2| 6| | | Multiplus & Multiplus II & MP-II GX 48/3000/35| 1| 3| 2| 6| |
| Multiplus 48/5000/70| 1| 3| 3| 9| | | Multiplus & Multiplus II & MP-II GX 48/5000/70| 1| 3| 3| 9| |
| Quattro 48/5000/70-100/100| 1| 3| 3| 9| | | Quattro 48/5000/70-100/100| 1| 3| 3| 9| |
| Quattro 48/8000/110-100/100| 1| 4| 5| 15| | | Quattro 48/8000/110-100/100| 1| 4| 5| 15| |
| Quattro 48/10000/140- 100/100| 1| 5| 6| 18| | | Quattro 48/10000/140- 100/100| 1| 5| 6| 18| |
| Quattro 48/15000/200- 100/100| 1| 6| 9| 27| | | Quattro 48/15000/200- 100/100| 1| 6| 9| 27| |
| EasySolar 48/3000/35-50 MPPT150/70| 1| 3| 2| 6| | | EasySolar & EasySolar-II 48/3000/35-50 MPPT| 1| 3| 2| 6| |
| EasySolar 48/5000/70-100 MPPT150/100| 1| 3| 3| 9| | | EasySolar 48/5000/70-100 MPPT| 1| 3| 3| 9| |
| |
| |
|Phases| Single Phase| Three Phase| Single Phase| Three Phase| | |Phases| Single Phase| Three Phase| Single Phase| Three Phase| |
| Inverter/Charger | Self-consumption | Self-consumption | Off-grid | Off-grid | | | Inverter/Charger | Self-consumption | Self-consumption | Off-grid | Off-grid | |
| Multiplus 48/3000/35| 1| 1| 1| 2| | | Multiplus & Multiplus II & MP-II GX 48/3000/35| 1| 1| 1| 2| |
| Multiplus 48/5000/70| 1| 1| 1| 3| | | Multiplus & Multiplus II & MP-II GX 48/5000/70| 1| 1| 1| 3| |
| Quattro 48/5000/70-100/100| 1| 1| 1| 3| | | Quattro 48/5000/70-100/100| 1| 1| 1| 3| |
| Quattro 48/8000/110-100/100| 1| 2| 2| 5| | | Quattro 48/8000/110-100/100| 1| 2| 2| 5| |
| Quattro 48/10000/140- 100/100| 1| 2| 2| 6| | | Quattro 48/10000/140- 100/100| 1| 2| 2| 6| |
| Quattro 48/15000/200- 100/100| 1| 3| 3| 7| | | Quattro 48/15000/200- 100/100| 1| 3| 3| 7| |
| EasySolar 48/3000/35-50 MPPT150/70| 1| 1| 1| 2| | | EasySolar & EasySolar-II 48/3000/35-50 MPPT150/70| 1| 1| 1| 2| |
| EasySolar 48/5000/70-100 MPPT150/100| 1| 1| 1| 3| | | EasySolar 48/5000/70-100 MPPT150/100| 1| 1| 1| 3| |
| |
|Phases| Single Phase| Three Phase| Single Phase| Three Phase| | |Phases| Single Phase| Three Phase| Single Phase| Three Phase| |
| Inverter/Charger | Self-consumption | Self-consumption | Grid-backup | Grid-backup | | | Inverter/Charger | Self-consumption | Self-consumption | Grid-backup | Grid-backup | |
| Multiplus 48/3000/35| 1| 2| 2| 6| | | Multiplus & Multiplus II & MP-II GX 48/3000/35| 1| 2| 2| 6| |
| Multiplus 48/5000/70| 1| 2| 4| 10| | | Multiplus & Multiplus II & MP-II GX 48/5000/70| 1| 2| 4| 10| |
| Quattro 48/5000/70-100/100| 1| 2| 4| 10| | | Quattro 48/5000/70-100/100| 1| 2| 4| 10| |
| Quattro 48/8000/110-100/100| 1| 3| 5| x| | | Quattro 48/8000/110-100/100| 1| 3| 5| x| |
| Quattro 48/10000/140- 100/100| 1| 4| 7| x| | | Quattro 48/10000/140- 100/100| 1| 4| 7| x| |
| Quattro 48/15000/200- 100/100| 1| 5| 10| x| | | Quattro 48/15000/200- 100/100| 1| 5| 10| x| |
| EasySolar 48/3000/35-50 MPPT150/70| 1| 2| 2| 6| | | EasySolar & EasySolar-II 48/3000/35-50 MPPT150/70| 1| 2| 2| 6| |
| EasySolar 48/5000/70-100 MPPT150/100| 1| 2| 4| 10| | | EasySolar 48/5000/70-100 MPPT150/100| 1| 2| 4| 10| |
| |
|Phases| Single Phase| Three Phase| Single Phase| Three Phase| | |Phases| Single Phase| Three Phase| Single Phase| Three Phase| |
| Inverter/Charger | On-Grid \ with Full Backup | On-Grid \ with inrush | Off-grid | Off-grid \ with inrush | | | Inverter/Charger | On-Grid \ with Full Backup | On-Grid \ with inrush | Off-grid | Off-grid \ with inrush | |
| Multiplus 48/3000/35| 1| 1 \ 2| 1| 1 \ 2| | | Multiplus & Multiplus II & MP-II GX 48/3000/35| 1| 1 \ 2| 1| 1 \ 2| |
| Multiplus 48/5000/70| 1| 2 \ 2| 1| 2| | | Multiplus & Multiplus II & MP-II GX 48/5000/70| 1| 2 \ 2| 1| 2| |
| Quattro 48/5000/70-100/100| 1| 2 \ 2| 1| 2| | | Quattro 48/5000/70-100/100| 1| 2 \ 2| 1| 2| |
| Quattro 48/8000/110-100/100| 1| 2 \ 3| 1| 2| | | Quattro 48/8000/110-100/100| 1| 2 \ 3| 1| 2| |
| Quattro 48/10000/140- 100/100| 1| 3 \ 4| 1| 3 \ 4| | | Quattro 48/10000/140- 100/100| 1| 3 \ 4| 1| 3 \ 4| |
| Quattro 48/15000/200- 100/100| 1 \ 2| 4 \ 6| 2| 4 \ 6| | | Quattro 48/15000/200- 100/100| 1 \ 2| 4 \ 6| 2| 4 \ 6| |
| EasySolar 48/3000/35-50 MPPT150/70| 1| 1| 1| 1| | | EasySolar & EasySolar-II 48/3000/35-50 MPPT150/70| 1| 1| 1| 1| |
| EasySolar 48/5000/70-100 MPPT150/100| 1| 2 \ 2| 1| 2| | | EasySolar 48/5000/70-100 MPPT150/100| 1| 2 \ 2| 1| 2| |
| |
|Phases| Single Phase| Three Phase| Single Phase| Three Phase| | |Phases| Single Phase| Three Phase| Single Phase| Three Phase| |
| Inverter/Charger | On-Grid | On-Grid | Off-grid | Off-grid \ with inrush | | | Inverter/Charger | On-Grid | On-Grid | Off-grid | Off-grid \ with inrush | |
| Multiplus 48/3000/35| 1| 2| 1| 4 \ 6| | | Multiplus & Multiplus II & MP-II GX 48/3000/35| 1| 2| 1| 4 \ 6| |
| Multiplus 48/5000/70| 1| 2| 2| 6 \ 8| | | Multiplus & Multiplus II & MP-II GX 48/5000/70| 1| 2| 2| 6 \ 8| |
| Quattro 48/5000/70-100/100| 1| 2| 2| 6 \ 8| | | Quattro 48/5000/70-100/100| 1| 2| 2| 6 \ 8| |
| Quattro 48/8000/110-100/100| 1| 2| 4| 8 \ 12| | | Quattro 48/8000/110-100/100| 1| 2| 4| 8 \ 12| |
| Quattro 48/10000/140- 100/100| 1| 4| 5| 12 \ 16| | | Quattro 48/10000/140- 100/100| 1| 4| 5| 12 \ 16| |
| Quattro 48/15000/200- 100/100| 1| 4| 7*| 16 \ 24| | | Quattro 48/15000/200- 100/100| 1| 4| 7*| 16 \ 24| |
| EasySolar 48/3000/35-50 MPPT150/70| 1| 2| 1| 4 \ 4| | | EasySolar & EasySolar-II 48/3000/35-50 MPPT150/70| 1| 2| 1| 4 \ 4| |
| EasySolar 48/5000/70-100 MPPT150/100| 1| 2| 2| 8 \ 8| | | EasySolar 48/5000/70-100 MPPT150/100| 1| 2| 2| 8 \ 8| |
| |
In a correctly configured system, the inverter will shut itself down before the batteries enter a self protective shut down state. | In a correctly configured system, the inverter will shut itself down before the batteries enter a self protective shut down state. |
| |
If your system is charged only with an AC-coupled PV inverter, this may prevent the AC-coupled PV inverter from starting up to recharge the batteries. Therefore it is strongly recommended that there is also either a generator or DC MPPT charge controller to provide DC bus power to bring the inverter back online to allow normal recharging to resume. | Therefore it is essential that there is also either a generator or DC MPPT charge controller for overall system stability. If your system is charged only with an AC-coupled PV inverter, this may prevent the AC-coupled PV inverter from starting up to recharge the batteries. |
| |
Even a single 100/20 48V MPPT charger unit with 2 x 60 cell solar panels would be sufficient to add this self correcting mechanism able to maintain the DC bus voltage and improve longterm system reliability considerably from accidental deep discharge and subsequent shut down. | Even a single 100/20 48V MPPT charger unit with 2 x 60 cell solar panels would be sufficient to add this self correcting mechanism able to maintain the DC bus voltage and improve longterm system reliability considerably from accidental deep discharge and subsequent shut down. |
===== 7. Example Wiring Diagram ===== | ===== 7. Example Wiring Diagram ===== |
| |