User Tools

Site Tools


battery_compatibility:bsl

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
battery_compatibility:bsl [2022-03-28 15:38] dylancbattery_compatibility:bsl [2024-02-21 14:22] (current) – [5.1 Victron MPPT charger settings] warwickchapman
Line 17: Line 17:
 __Special note for Off-Grid systems__ __Special note for Off-Grid systems__
  
-For Off-grid systems, its strongly recommend to make sure there is a minimum of DC-Coupled PV (= MPPT Solar Charger) in the system. Ie. not only AC-Coupled PV. Also, minimum battery configuration, and factor 1.0 are always important to adhere to, and even more so in case of Off-grid systems. Both BSL and Victron will be reluctant or even refusing to give support to systems that are not sized according to the minimum specified configurations.+For Off-grid systems, its strongly recommend to make sure there is a minimum of a single DC-Coupled PV (= MPPT Solar Charger) in the system. Ie. not only AC-Coupled PV. Also, minimum battery configuration, and factor 1.0 are always important to adhere to, and even more so in case of Off-grid systems. Both BSL and Victron will be reluctant or even refusing to give support to systems that are not sized according to the minimum specified configurations.
  
 === 1.2 A GX device is required, eg Cerbo GX, etc ===  === 1.2 A GX device is required, eg Cerbo GX, etc === 
Line 47: Line 47:
  
 It should be noted that one should always connect the battery before connecting the solar input to any MPPT.  It should be noted that one should always connect the battery before connecting the solar input to any MPPT. 
 +
 +The CAN-bus baud rate is 500kbis/s for communication between BSL batteries and any GX device. 
  
 === Battery compatibility === === Battery compatibility ===
Line 53: Line 55:
 ^ BSLBATT type ^ ^ BSLBATT type ^
 | B-LFP48-100E   | | B-LFP48-100E   |
-| B-LFP48-120E       | +| B-LFP48-125E       |
-| B-LFP48-200PW       |+
 | B-LFP48-160E       | | B-LFP48-160E       |
 +| B-LFP48-200PW       |
 +
  
 ===== 2. Minimum Battery Sizing ===== ===== 2. Minimum Battery Sizing =====
Line 63: Line 66:
 It should also be noted that these are the minimum requirements for the BSL battery range and that each unit can be paralleled many times over. Please consult the relevant manual on how many units can be placed in parallel.  It should also be noted that these are the minimum requirements for the BSL battery range and that each unit can be paralleled many times over. Please consult the relevant manual on how many units can be placed in parallel. 
  
-The table below shows the minimum number of battery modules required for the specified inverter/charger configuration:+The table below shows the __**minimum**__ number of battery modules required for the specified inverter/charger configuration:
  
 === Battery Modules Required - 5.1kWh/100Ah === === Battery Modules Required - 5.1kWh/100Ah ===
Line 123: Line 126:
 ===== 3. CAN-Bus wiring between battery and GX device ===== ===== 3. CAN-Bus wiring between battery and GX device =====
  
-In order to connect your battery to the relevant GX device, one must utilize a "Type B" cable, the Victron part number for this cable is : ASS030720018/50.(Black to inverter/GX device, red to battery).+In order to connect your battery to the relevant GX device, one must utilize a "Type B" cable, the Victron part number for this cable is : ASS030720018.
  
 One should always terminate the CAN port on the GX device when it comes to installing BSL batteries.  One should always terminate the CAN port on the GX device when it comes to installing BSL batteries. 
Line 160: Line 163:
  
 === 4.5 Specific manuals for various models of battery: ===   === 4.5 Specific manuals for various models of battery: ===  
-  * 5.1kWh battery- {{ :battery_compatibility:bsl_5_1_manual_v1.pdf |}}  
-  * 6.4kWh battery- {{ :battery_compatibility:bsl_6_4_manual_v1.pdf |}}  
-  * 8.2kWh battery- {{ :battery_compatibility:bsl_8_2_manual_v1.pdf |}}  
-  * 10.2kWh battery- {{ :battery_compatibility:bsl_power_wall_manual_v1.pdf |}} 
- 
- 
  
 +  * 5.1kWh battery- {{ :battery_compatibility:bslbatt_5.1k_victron_setup_guide_v1.3.pdf |}}
 +  * 6.4kWh battery- {{ :battery_compatibility:bslbatt_6.4kw_victron_setup_guide_v1.3.pdf |}}
 +  * 7kWh battery- {{ :battery_compatibility:bslbatt_7kw_victron_setup_guide_v1.3.pdf |}}
 +  * 8.2kWh battery- {{ :battery_compatibility:bslbatt_8.2kw_8.8kw_victron_setup_guide_v1.3.pdf |}}
 +  * 10.2kWh battery- {{ :battery_compatibility:bslbatt_10.2_power_wall_victron_setup_guide_v1.3.pdf |}}
 +  * 15kWh battery- {{ :battery_compatibility:bslbatt_15kw_slimline_victron_setup_guide_v1.3.pdf |}}
 +  * Powerline-5 battery- {{ :battery_compatibility:bslbatt_powerline-5_victron_setup_guide_v1.3.pdf |}}
  
 ===== 5. Solar Charging ===== ===== 5. Solar Charging =====
Line 173: Line 177:
  
 Victron MPPT charge characteristics are automatically configured & governed by the [[venus-os:start|GX device]]. The settings below are a precautionary measure only: Victron MPPT charge characteristics are automatically configured & governed by the [[venus-os:start|GX device]]. The settings below are a precautionary measure only:
 +
 +Select Battery > Preset > Smart Lithium
  
 ^ MPPT Parameter ^ Setting ^ ^ MPPT Parameter ^ Setting ^
 |Battery voltage     |48V| |Battery voltage     |48V|
 |Absorption voltage   |55V| |Absorption voltage   |55V|
 +|Float voltage   |55V|
 +
 +The MPPT should also be configured correctly in case of the GX device failing and thus not being able to throttle up or down the charging currents and voltages.  
  
 ===== 6. Battery configured correctly ===== ===== 6. Battery configured correctly =====
battery_compatibility/bsl.1648474684.txt.gz · Last modified: 2022-03-28 15:38 by dylanc