battery_compatibility:bsl
Differences
This shows you the differences between two versions of the page.
| Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
| battery_compatibility:bsl [2022-03-28 13:38] – dylanc | battery_compatibility:bsl [2026-10-12 03:59] (current) – guy_stewart | ||
|---|---|---|---|
| Line 17: | Line 17: | ||
| __Special note for Off-Grid systems__ | __Special note for Off-Grid systems__ | ||
| - | For Off-grid systems, its strongly recommend to make sure there is a minimum of DC-Coupled PV (= MPPT Solar Charger) in the system. Ie. not only AC-Coupled PV. Also, minimum battery configuration, | + | For Off-grid systems, its strongly recommend to make sure there is a minimum of a single |
| === 1.2 A GX device is required, eg Cerbo GX, etc === | === 1.2 A GX device is required, eg Cerbo GX, etc === | ||
| Line 42: | Line 42: | ||
| Some of our Solar Chargers feature a VE.Direct communication port, some feature a VE.Can communication port, and some feature both. Both of these types of communication ports can be used to connect the Solar charger to the GX Device. Such connection is mandatory, because it is used to regulate charge currents and voltages. | Some of our Solar Chargers feature a VE.Direct communication port, some feature a VE.Can communication port, and some feature both. Both of these types of communication ports can be used to connect the Solar charger to the GX Device. Such connection is mandatory, because it is used to regulate charge currents and voltages. | ||
| - | When planning to use the VE.Can communications port to connect the Solar Charger(s), make sure to select a GX Device that has sufficient CAN-Bus ports. The Color Control GX has only one such port, its VE.Can port, and is therefor not suitable. | + | When planning to use the VE.Can communications port to connect the Solar Charger(s), make sure to select a GX Device that has sufficient CAN-Bus ports. The Color Control GX has only one such port, its VE.Can port, and is therefor not suitable. |
| (*) with exception of the models “BlueSolar MPPT 150/70 CAN-bus” and “BlueSolar MPPT 150/85 CAN-bus” which are end-of-life since 2019. Legacy systems, historically installed with this configuration using the allow to charge contacts may be possible, speak to your dealer for more information. | (*) with exception of the models “BlueSolar MPPT 150/70 CAN-bus” and “BlueSolar MPPT 150/85 CAN-bus” which are end-of-life since 2019. Legacy systems, historically installed with this configuration using the allow to charge contacts may be possible, speak to your dealer for more information. | ||
| It should be noted that one should always connect the battery before connecting the solar input to any MPPT. | It should be noted that one should always connect the battery before connecting the solar input to any MPPT. | ||
| + | |||
| + | The CAN-bus baud rate is 500kbis/s for communication between BSL batteries and any GX device. | ||
| === Battery compatibility === | === Battery compatibility === | ||
| - | The following | + | All BSL batteries are supported |
| - | ^ BSLBATT type ^ | + | |
| - | | B-LFP48-100E | + | |
| - | | B-LFP48-120E | + | |
| - | | B-LFP48-200PW | + | |
| - | | B-LFP48-160E | + | |
| ===== 2. Minimum Battery Sizing ===== | ===== 2. Minimum Battery Sizing ===== | ||
| Line 63: | Line 61: | ||
| It should also be noted that these are the minimum requirements for the BSL battery range and that each unit can be paralleled many times over. Please consult the relevant manual on how many units can be placed in parallel. | It should also be noted that these are the minimum requirements for the BSL battery range and that each unit can be paralleled many times over. Please consult the relevant manual on how many units can be placed in parallel. | ||
| - | The table below shows the minimum number of battery modules required for the specified inverter/ | + | The table below shows the __**minimum**__ number of battery modules required for the specified inverter/ |
| === Battery Modules Required - 5.1kWh/ | === Battery Modules Required - 5.1kWh/ | ||
| Line 123: | Line 121: | ||
| ===== 3. CAN-Bus wiring between battery and GX device ===== | ===== 3. CAN-Bus wiring between battery and GX device ===== | ||
| - | In order to connect your battery to the relevant GX device, one must utilize a "Type B" cable, the Victron part number for this cable is : ASS030720018/50.(Black to inverter/GX device, red to battery). | + | In order to connect your battery to the relevant GX device, one must utilize a "Type B" cable, the Victron part number for this cable is : ASS030720018. |
| One should always terminate the CAN port on the GX device when it comes to installing BSL batteries. | One should always terminate the CAN port on the GX device when it comes to installing BSL batteries. | ||
| Line 135: | Line 133: | ||
| | Charge curve | Fixed | | Charge curve | Fixed | ||
| | Absorption voltage | | Absorption voltage | ||
| - | | Absorption | + | | Float voltage (1) |
| - | | Float voltage (1) | 55 V | | + | |
| | Absorption time | 1 Hr | | | Absorption time | 1 Hr | | ||
| Line 143: | Line 140: | ||
| In the Inverter tab of VEConfigure | In the Inverter tab of VEConfigure | ||
| ^VEConfigure Inverter Parameter | ^VEConfigure Inverter Parameter | ||
| - | |DC input low shut-down | 47V| | + | |DC input low shut-down | 48V | |
| - | |DC input low restart | + | |DC input low restart |
| - | |DC input low pre-alarm* | 51V| | + | |DC input low pre-alarm* | 51V | |
| === 4.3 ESS Settings === | === 4.3 ESS Settings === | ||
| ^ ESS Parameter ^ Settings ^ | ^ ESS Parameter ^ Settings ^ | ||
| - | |Sustain voltage. | + | |Sustain voltage. |
| - | |Dynamic cut-off values | set all values to 47V.| | + | |Dynamic cut-off values | Set all values to 47V | |
| - | |Restart offset: | + | |Restart offset: |
| + | |Voltage to restart PV: | 53.5V | | ||
| === 4.4 All Settings === | === 4.4 All Settings === | ||
| Line 160: | Line 158: | ||
| === 4.5 Specific manuals for various models of battery: === | === 4.5 Specific manuals for various models of battery: === | ||
| - | * 5.1kWh battery- {{ : | ||
| - | * 6.4kWh battery- {{ : | ||
| - | * 8.2kWh battery- {{ : | ||
| - | * 10.2kWh battery- {{ : | ||
| - | |||
| - | |||
| + | * 5.1kWh battery- {{ : | ||
| + | * 6.4kWh battery- {{ : | ||
| + | * 7kWh battery- {{ : | ||
| + | * 8.2kWh battery- {{ : | ||
| + | * 10.2kWh battery- {{ : | ||
| + | * 15kWh battery- {{ : | ||
| + | * Powerline-5 battery- {{ : | ||
| ===== 5. Solar Charging ===== | ===== 5. Solar Charging ===== | ||
| Line 173: | Line 172: | ||
| Victron MPPT charge characteristics are automatically configured & governed by the [[venus-os: | Victron MPPT charge characteristics are automatically configured & governed by the [[venus-os: | ||
| + | |||
| + | Select Battery > Preset > Smart Lithium | ||
| ^ MPPT Parameter ^ Setting ^ | ^ MPPT Parameter ^ Setting ^ | ||
| |Battery voltage | |Battery voltage | ||
| |Absorption voltage | |Absorption voltage | ||
| + | |Float voltage | ||
| + | |||
| + | The MPPT should also be configured correctly in case of the GX device failing and thus not being able to throttle up or down the charging currents and voltages. | ||
| ===== 6. Battery configured correctly ===== | ===== 6. Battery configured correctly ===== | ||
battery_compatibility/bsl.1648474684.txt.gz · Last modified: by dylanc