- | ==== 6. Configure MPPT ==== | + | |
+ | ==== **6.** **BlueNova Energy battery setup with DVCC enabled** | ||
+ | (DVCC - Distributed Voltage and Current Control) ==== | ||
+ | |||
+ | Introduction and features | ||
+ | |||
+ | Enabling DVCC in a setup containing a BlueNova Energy battery, | ||
+ | |||
+ | The GX device | ||
+ | |||
+ | |||
+ | {{https:// | ||
+ | |||
+ | |||
+ | {{https:// | ||
+ | |||
+ | |||
+ | Shared Voltage Sense (SVS) | ||
+ | Works with VE.Bus devices and VE.Direct Solar Chargers. | ||
+ | |||
+ | The system automatically selects the best available voltage measurement. It will use the voltage from the BlueNova Energy | ||
+ | The voltage displayed on the GUI reflects the same voltage measurement. | ||
+ | |||
+ | **Shared Voltage Sense** (SVS) is by default enabled when DVCC is enabled. It can be disabled with a switch in the Settings → System Setup menu. | ||
+ | |||
+ | **Limit charge current** | ||
+ | This is a user-configurable maximum charge current setting and can, in majority of cases, be | ||
+ | |||
+ | To enable or disable DVCC, see Settings → System Setup in the menus. | ||
+ | |||
+ | |||
+ | **DVCC Requirements :** | ||
+ | |||
+ | |||
+ | Battery compatilibity | ||
+ | |||
+ | DVCC has extensively been tested on BlueNova Energy batteries and is therefore fully supported . | ||
+ | |||
+ | |||
+ | **Firmware versions :** | ||
+ | |||
+ | Do not use DVCC in cases where these requirements(Victron) are not met. In all cases we recommend to install the latest available firmware during commissioning. Once running well, there is no need to pro- actively update firmware without reason. In case of difficulty, the first action is to update firmware. | ||
+ | |||
+ | |||
+ | **Required minimum firmware versions:** | ||
+ | |||
+ | |||
+ | BlueNova Energy | ||
+ | |||
+ | BlueNova Energy BMMC : V2.6c | ||
+ | |||
+ | Multi/ | ||
+ | |||
+ | MultiGrid: 424 | ||
+ | |||
+ | CCGX / Venus GX: v2.12 VE.Direct MPPTs: v1.29 | ||
+ | |||
+ | VE.Can MPPT Solar Chargers cannot be used: they do not yet support the new control mechanisms. | ||
+ | Lynx Ion + Shunt: v2.04 Lynx BMS: v1.09 | ||
+ | |||
+ | In case of an ESS System, the ESS Assistant needs to be version 164 or later (Released in November 2017). | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | |||
+ | ==== 7. Configure MPPT ==== | ||
- Disable Autodetect voltage | - Disable Autodetect voltage | ||
- Set Battery voltage to 48V. | - Set Battery voltage to 48V. |