Programming via PROG pin to GND pin method
Requirements prior to programming:
The battery positive must be connected to the IN terminal. Do not connect the OUT terminal yet.
The included ground wire must be connected to the battery minus and the GND terminal of the Smart BatteryProtect 12/24V.
The wire loop in the remote on/off terminal block must be removed.
Programming procedure:
Use a wire loop or a wired switch (preferably a push button) between the PROG pin and the GND pin.
While there is a connection between the PROG pin and the GND pin, the 7-segment display will first step through the shutdown and restart voltage combinations, as indicated by the numbers 0..9 (see the Programming table).
Remove the wire loop or release the push button when the desired voltage mode is displayed.
The display will confirm the chosen voltage and default mode (A) twice.
Reconnect the wire loop or press the push button again, if a different operation mode (B, C or D) is required (see the Programming table).
Disconnect the wire loop or release the push button when the required mode is displayed.
The display will confirm the chosen voltage and operation mode twice.
The PIN code can be reset by selecting the P option. Bluetooth pairing information needs to be removed from any previously paired devices after selecting this option.
Bluetooth can be disabled/re-enabled by selecting F (enable) or H (disable).
Push button wired to program the Smart BatteryProtect