 The configured coefficient is in mV per degree Celsius for the whole battery bank, not per cell. The base temperature for the compensation is 25°C (77°F), as shown in the chart below. The configured coefficient is in mV per degree Celsius for the whole battery bank, not per cell. The base temperature for the compensation is 25°C (77°F), as shown in the chart below.
  
-{{:​victronconnect:​mppt-tempcomp-graph3.png?​350|Battery voltage adjustment based on battery temperature (14.4V as setpoint, compensation factor = 16.2mV/​ºC)}}+{{:​victronconnect:​mppt-tempcomp-graph4.png?​350|Battery voltage adjustment based on battery temperature (14.4V as setpoint, compensation factor = 16.2mV/​ºC)}}
  
 With a [[:​smart_battery_sense_manual|Smart Battery Sense]] is installed; the actual battery temperature will be used for compensation;​ throughout the day. With a [[:​smart_battery_sense_manual|Smart Battery Sense]] is installed; the actual battery temperature will be used for compensation;​ throughout the day.