===== Solar and wind priority ===== | ===== Solar and wind priority ===== | ||
- | NOTE: this is a new feature that is being rolled out in steps: | + | NOTE: this is a new feature that is being rolled out in steps, and currently in beta. We'll be testing this over the summer period; and once stable announce it officially. |
- | | + | Status in details: |
- | - VEConfigure, | + | |
- | - VictronConnect, | + | - VEConfigure, |
- | - Venus OS Normal GUI, add user control to override it in case a full charge from shore is needed. | + | - VictronConnect, |
+ | - Venus OS Normal GUI, add user control to override it in case a full charge from shore is needed. | ||
- Venus OS HTML5 GUI, add user control to override it in case a full charge from shore is needed - pending. | - Venus OS HTML5 GUI, add user control to override it in case a full charge from shore is needed - pending. | ||
- VRM Dashboard controls, same - pending. | - VRM Dashboard controls, same - pending. | ||
- | |||
- | In other words, per late June 2023, it is possible to use this feature. A while later, hopefully already in July, we’ll have added the user option to - temporarily - override it for moments when a full charge from shore is required. | ||
- | |||
==== 1. Feature description ==== | ==== 1. Feature description ==== | ||
Line 31: | Line 29: | ||
==== 2. Config instructions ==== | ==== 2. Config instructions ==== | ||
- | DRAFT - TO BE COMPLETED | + | === Step 1 - Firmware update |
- | + | ||
- | === Step 1 - Firmware update === | + | |
WARNING: updating the firmware of this product range is strongly advised to be carried out by trained personnel only. Doing the update will cause all settings to be reset to their default: we therefor advise to save the settings before updating and after updating reinstall the configuration. | WARNING: updating the firmware of this product range is strongly advised to be carried out by trained personnel only. Doing the update will cause all settings to be reset to their default: we therefor advise to save the settings before updating and after updating reinstall the configuration. | ||
Line 39: | Line 35: | ||
Update VE.Bus firmware to 506 or higher: | Update VE.Bus firmware to 506 or higher: | ||
- | * To do that locally, using an MK3-USB adapter, use VictronConnect. [[https:// | + | * Install the VictronConnect beta version V5.92beta1 or later, available [[https:// |
- | * To do that remotely, over the internet, see [[https:// | + | |
+ | |||
+ | For now, VictronConnect beta is the only source for the new 506 firmware, therefor the firmware update through VRM option is not possible at the moment. | ||
+ | |||
+ | * To update | ||
+ | * <del>To do that remotely, over the internet, see [[https:// | ||
=== Step 2 - Enable the mode === | === Step 2 - Enable the mode === | ||
+ | == VictronConnect == | ||
+ | The setting is available in VictronConnect in the advanced tab of the settings: | ||
+ | {{ : | ||
+ | |||
+ | == VeConfigure == | ||
The setting is enabled in VEConfigure, | The setting is enabled in VEConfigure, | ||
{{ : | {{ : | ||
- | Once enabled | + | These are the recommended sustain voltages: |
+ | |||
+ | ^ System voltage ^ LiFePO4 ^ Lead (AGM, Gel) ^ | ||
+ | | 12V | 13.0V | Float minus 0.2V | | ||
+ | | 24V | 26.0V | Float minus 0.3V| | ||
+ | | 48V | 52.0V | Float minus 0.4V| | ||
+ | |||
+ | For Lithium, setting Sustain | ||
+ | |||
+ | For Lead ... ? | ||
=== Step 3 - Check further settings === | === Step 3 - Check further settings === | ||
Line 54: | Line 69: | ||
- if the Storage setting is enabled, then after 12 hours of float, the system will go to storage | - if the Storage setting is enabled, then after 12 hours of float, the system will go to storage | ||
- | - repeated absorption interval. | + | - repeated absorption interval, defaults to seven days. |
==== 3. User instructions ==== | ==== 3. User instructions ==== |
ve.bus/skip-absorption.txt · Last modified: 2023-07-28 17:25 by mvader