User Tools

Site Tools


ve.bus:manual_parallel_and_three_phase_systems

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
Next revisionBoth sides next revision
ve.bus:manual_parallel_and_three_phase_systems [2019-12-09 13:10] – [Configuration] mvaderve.bus:manual_parallel_and_three_phase_systems [2020-02-13 12:27] mvader
Line 44: Line 44:
 Also beware of sizing the battery cable and jumpers between cells/batteries. Also beware of sizing the battery cable and jumpers between cells/batteries.
  
-For units in parallel: Both the DC and AC wiring needs to be symmetrical per phase: use the same length, type and cross-section to every unit in the phase. To make this easy, use a bus-bar or power-post before and after the inverter/chargers.+For units in parallel: Both the DC and AC wiring needs to be symmetrical per phase: use the same length, type and cross-section to every unit in the phase. To make this easy, use a bus-bar or power-post before and after the inverter/chargers. Also, apply the same torque on all connections.
  
-For units in parallel: use one AC fuse for all units on that phase. Both on the input, and on the output. Multiple fuses which are mechanically connected together is ok: that is also one fuse.+With regards to AC fusing, each unit needs to be fused individually. Both on its AC-out and AC-in. Multiple circuit breakers which are mechanically connected together is OK: that is also one fuse. Make sure to use the same type of fuse on each unit due to same resistance.
  
-For DC, one fuse per phase is best. If a big single fuse is not available, use one fuse per unit. Same type of fuse due to same resistance.+With regards to DC fusingeach unit needs to be fused individuallyMake sure to use the same type of fuse on each unit due to same resistance
 + 
 +For both AC and DC fusing and protection, consult the product manual for details and recommended ratings.
  
 Beware of phase rotation between the inverter and AC in. When wired in a rotation that is different to the programming of the Multis, the system will not accept the mains input and only operates in inverter mode. [[https://www.victronenergy.com/live/ccgx:start#phase_rotation_warning|If a GX device is connected, it will signal a phase rotation alarm]]. In that case swap two phases to correct it, or re-program the units to match the wiring rotation.  Beware of phase rotation between the inverter and AC in. When wired in a rotation that is different to the programming of the Multis, the system will not accept the mains input and only operates in inverter mode. [[https://www.victronenergy.com/live/ccgx:start#phase_rotation_warning|If a GX device is connected, it will signal a phase rotation alarm]]. In that case swap two phases to correct it, or re-program the units to match the wiring rotation. 
Line 104: Line 106:
   * Country / grid code standard and other grid related values (AC high/ low values)   * Country / grid code standard and other grid related values (AC high/ low values)
   * DC input low shut-down values.   * DC input low shut-down values.
 +
 +Charger settings (voltage and current limits) are overridden if DVCC is configured and if a CANBus BMS is active in the system.
  
 A quick way to make settings in all units is the 'send to all units' feature. You'll see the option after making the changes to the first unit. A quick way to make settings in all units is the 'send to all units' feature. You'll see the option after making the changes to the first unit.
ve.bus/manual_parallel_and_three_phase_systems.txt · Last modified: 2024-02-09 13:07 by jpasop

Donate Powered by PHP Valid HTML5 Valid CSS Driven by DokuWiki