LOM detection comes in two flavours: **Type A** and **Type B**. | LOM detection comes in two flavours: **Type A** and **Type B**. | ||
- | **Type A** is the strongest form LOM detection, which results | + | **Type A** is the strongest form of LOM detection |
- | **Type B** has a more soft approach. Resulting in a slightly longer detection time. Still acceptable in several countries | + | **Type B** has a more soft approach |
+ | On generators, and also with installations having | ||
For generators on which also **Type B** does not work, see Disabling LOM. | For generators on which also **Type B** does not work, see Disabling LOM. | ||
Line 77: | Line 78: | ||
Some, bigger or better quality generators, will be able to work with LOM **Type B**. For other less stable generators it will be required to disable LOM entirely. In that case make the installation such that it is still safe: no simple extensions cords, use enclosed wiring cabinets with warnings on the outside and/or an external ENS. | Some, bigger or better quality generators, will be able to work with LOM **Type B**. For other less stable generators it will be required to disable LOM entirely. In that case make the installation such that it is still safe: no simple extensions cords, use enclosed wiring cabinets with warnings on the outside and/or an external ENS. | ||
+ | More information here: https:// | ||
==== Q4: I use ESS, but have disabled feed-back, is a grid-code still required? ==== | ==== Q4: I use ESS, but have disabled feed-back, is a grid-code still required? ==== | ||