Previous revision
system_integration:hub4_grid_parallel_external_control_loop [2016-10-03 11:07] – [2.2 Control through MQTT or CCGX scripting] mvadersystem_integration:hub4_grid_parallel_external_control_loop [2019-01-22 10:16] (current) – external edit 127.0.0.1
Line 4: Line 4:
  
 Note that it is also possible to run a Victron grid parallel storage system without designing and implementing your own control loop, logic or measurements. See the  [[system_integration:hub4_grid_parallel|Hub-4 manual]]. Note that it is also possible to run a Victron grid parallel storage system without designing and implementing your own control loop, logic or measurements. See the  [[system_integration:hub4_grid_parallel|Hub-4 manual]].
 +
 +Note that though this page mentions Hub-4, which is deprecated, it also applies to ESS.
 +
 ===== 1. Overview of Hub-4 operating modes ===== ===== 1. Overview of Hub-4 operating modes =====
  
Line 64: Line 67:
  
 === A) Via ModbusTCP === === A) Via ModbusTCP ===
-See above mentioned register numbers.+See above mentioned register numbers. Use ModbusTCP unitid 100.
  
 === B) Via MQTT === === B) Via MQTT ===
Line 194: Line 197:
   * As an alternative to running the control loop externally, using ModbusTCP, it is also possible to run code on the CCGX itself and update the AcPowerSetpoint via D-Bus. We have one customer that is running a MQTT client on the CCGX, written in Python, that gets the control-loop output as updates from a MQTT broker. And the Python script sends them to the Multi, using D-Bus service com.victronenergy.vebus.ttyO1, and path /Hub4/AcPowerSetpoint   * As an alternative to running the control loop externally, using ModbusTCP, it is also possible to run code on the CCGX itself and update the AcPowerSetpoint via D-Bus. We have one customer that is running a MQTT client on the CCGX, written in Python, that gets the control-loop output as updates from a MQTT broker. And the Python script sends them to the Multi, using D-Bus service com.victronenergy.vebus.ttyO1, and path /Hub4/AcPowerSetpoint
      
 +
  