User Tools

Site Tools


system_integration:hub4_grid_parallel

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
system_integration:hub4_grid_parallel [2016-08-26 13:52] – [6. Multi/Quattro configuration] mvadersystem_integration:hub4_grid_parallel [2019-01-22 10:16] (current) – external edit 127.0.0.1
Line 1: Line 1:
-====== Hub-4 / grid parallel - manual ======+====== Hub-4 / grid parallel - manual DEPRECATED ====== 
 + 
 +Do not use Hub-4 for new installs. It is deprecated in favor of [[ess:start|ESS]]. 
 + 
 + 
 +===== OLD MANUAL ===== 
 + 
 +===== 1. Introduction & features =====
  
 Note: make sure to always update all components to the latest software when making a new installation. Note: make sure to always update all components to the latest software when making a new installation.
  
 === Introduction === === Introduction ===
-Hub-4 is a Grid-parallel Energy Storage system, using the Multi or Quattro bidirectional inverter/charger as its main component. It optimizes self-consumption: at times when there is excess PV power, the PV energy is stored in the battery. And that stored energy is then to power the loads at times when there is a shortage of PV power. +Hub-4 is a Grid-parallel Energy Storage system, using the Multi or Quattro bidirectional inverter/charger as its main component. It optimizes self-consumption: at times when there is excess PV power, the PV energy is stored in the battery. That stored energy is then used to power the loads at times when there is a shortage of PV power.
  
-The system is managed by the [[https://www.victronenergy.com/panel-systems-remote-monitoring/color-control|Color Control GX]] (CCGX), which also provides extensive monitoring, both locally and remotely via our [[https://vrm.victronenergy.com/|VRM Portal]] and the [[https://www.victronenergy.com/support-and-downloads/software#victron-vrm-app|VRM App]]. The VRM app is available for both iOS and Android.+The system is managed by the [[https://www.victronenergy.com/panel-systems-remote-monitoring/color-control|Color Control GX]] (CCGX), which also provides extensive monitoring, both locally and remotely via our [[https://vrm.victronenergy.com/|VRM Portal]] and the [[https://www.victronenergy.com/support-and-downloads/software#victron-vrm-app|VRM App]].
  
 === Schematic overview === === Schematic overview ===
- +{{ :system_integration:hub4_pv-out_mppt_schema.png?nolink |}}
-{{ :system_integration:hub4-jan2016.png?nolink |}} +
  
 === Features === === Features ===
   * Grid parallel energy storage system that optimizes self consumption.   * Grid parallel energy storage system that optimizes self consumption.
   * Wide range of available inverter/chargers: 800 VA to 10.000 VA in 12, 24 and 48 VDC.   * Wide range of available inverter/chargers: 800 VA to 10.000 VA in 12, 24 and 48 VDC.
-  * Flexible:+  * Single, split- or three-phase:
     - a single phase inverter/charger installation in a single-phase system     - a single phase inverter/charger installation in a single-phase system
     - a single phase inverter/charger installation in a multi-phase system     - a single phase inverter/charger installation in a multi-phase system
     - a split- or three-phase inverter/charger system in a multi-phase system     - a split- or three-phase inverter/charger system in a multi-phase system
 +  * Flexible PV type: use AC-Coupled PV in parallel to the Multi, AC-Coupled PV on the output of the Multi, DC-Coupled PV, or a combination of those three
   * Both wired and a wireless connection to the meter central distribution box is possible.   * Both wired and a wireless connection to the meter central distribution box is possible.
   * (optional) No-break UPS output.   * (optional) No-break UPS output.
   * (optional) Phase compensation.   * (optional) Phase compensation.
   * Built-in anti-islanding / loss of mains detection. Currently certified for limited number of countries/models, more certification coming.   * Built-in anti-islanding / loss of mains detection. Currently certified for limited number of countries/models, more certification coming.
-  * No restrictions on PV Array size.+  * No restrictions on installed PV power on the AC Input
   * No minimum or maximum battery size.   * No minimum or maximum battery size.
   * Suitable for many battery types.   * Suitable for many battery types.
   * Three operating modes, from basic to custom, covering both standard and custom systems.   * Three operating modes, from basic to custom, covering both standard and custom systems.
   * Free usage of the [[https://vrm.victronenergy.com|VRM Portal]] and the [[https://www.victronenergy.com/support-and-downloads/software#victron-vrm-app|VRM App]] for remote monitoring.   * Free usage of the [[https://vrm.victronenergy.com|VRM Portal]] and the [[https://www.victronenergy.com/support-and-downloads/software#victron-vrm-app|VRM App]] for remote monitoring.
-  * Winter switchkeep batteries charged in periods where there is continuous shortage of solar power+  * BatteryLifeextend battery life time, and also be prepared for grid outage
  
 === Operating modes === === Operating modes ===
Line 35: Line 41:
   - Advanced \\ Same as standard, but more flexibility is given to implement time shifting, load management or other energy management optimization algorithms. Either by ModbusTCP commands or by running additional self implemented code on the Color Control GX. Often the best of both worlds: complete flexibility and benefit from the VRM Portal and all other functionality already available on the CCGX, without having to add additional cost of extra PLCs or other control modules. [[system_integration:hub4_grid_parallel_external_control_loop|more information]].   - Advanced \\ Same as standard, but more flexibility is given to implement time shifting, load management or other energy management optimization algorithms. Either by ModbusTCP commands or by running additional self implemented code on the Color Control GX. Often the best of both worlds: complete flexibility and benefit from the VRM Portal and all other functionality already available on the CCGX, without having to add additional cost of extra PLCs or other control modules. [[system_integration:hub4_grid_parallel_external_control_loop|more information]].
   - Custom \\ Customer self implements their control loop and grid measurements, and uses the MultiPlus and/or Quattros as simple, remote controllable, bidirectional inverter/chargers that can be set to either charge or discharge an x amount of Watts. [[system_integration:hub4_grid_parallel_external_control_loop|for more information]].   - Custom \\ Customer self implements their control loop and grid measurements, and uses the MultiPlus and/or Quattros as simple, remote controllable, bidirectional inverter/chargers that can be set to either charge or discharge an x amount of Watts. [[system_integration:hub4_grid_parallel_external_control_loop|for more information]].
-===== 1. Required parts =====+===== 2. Required parts =====
 ^ Part no.      ^ Description            ^ ^ Part no.      ^ Description            ^
 | PMP, CMP or QUA | Multi or Quattro inverter/charger (see Note 1 below) |  | PMP, CMP or QUA | Multi or Quattro inverter/charger (see Note 1 below) | 
-| REL200100000 Wired AC sensor - 1 and 3-phase - max 65A per phase |+| REL200100000 Energy Meter - 1 and 3-phase - max 65A per phase |
 | BPP000300100R | Color Control GX | | BPP000300100R | Color Control GX |
 | ASS03006xxxx  | RJ-45 UTP Cable | | ASS03006xxxx  | RJ-45 UTP Cable |
Line 60: Line 66:
 Notes: Notes:
   - The Multi or Quattro used needs to be a recent type with the new microprocessor (26xxxxx or 27xxxxx). All units currently shipping have this new microprocessor. Also, the Multi or Quattro needs to run the latest 4xx firmware. Contact your Victron representative for the firmware files. Update instructions are [[updating_firmware:updating_ve.bus_products|here]].   - The Multi or Quattro used needs to be a recent type with the new microprocessor (26xxxxx or 27xxxxx). All units currently shipping have this new microprocessor. Also, the Multi or Quattro needs to run the latest 4xx firmware. Contact your Victron representative for the firmware files. Update instructions are [[updating_firmware:updating_ve.bus_products|here]].
-  - The RS485 to USB interface cable from the CCGX to the AC sensor can be extended up to 100 meters max. + 
-  - The REL200100000 is the EM24DINAV93XISX from Carlo Gavazzi. Other EM24 models from Carlo Gavazzi can also be used, as the communication is the same. For example the EM24DINAV53DISX, which uses Current Transformers and can therefore work in systems > 63A per phase. Note that this model is not stocked by Victron Energy, we recommend to purchase it locally. +===== 3. Battery, inverter/charger and PV dimensioning =====
-===== 2. Battery, inverter/charger and PV dimensioning =====+
  
 === Battery size === === Battery size ===
Line 80: Line 85:
  
 Note that even in an Hub-4 installation, it is possible to connect AC-Coupled PV power on the output of the inverter/charger. In that case, make sure add the PV Inverter Assistant to the list of installed Assistants in VEConfigure. Note that even in an Hub-4 installation, it is possible to connect AC-Coupled PV power on the output of the inverter/charger. In that case, make sure add the PV Inverter Assistant to the list of installed Assistants in VEConfigure.
-===== 3. Single vs multi phase installations ===== +===== 4. Single vs multi phase installations ===== 
-==== 3.1 Single phase inverter/charger system ====+==== 4.1 Single phase inverter/charger system ====
 === Phase compensation === === Phase compensation ===
 Phase compensation, for a single phase inverter/charger installation, part of a multi phase system.  Phase compensation, for a single phase inverter/charger installation, part of a multi phase system. 
Line 96: Line 101:
 Enabling or disabling phase compensation is done in the Hub-4 settings on the Color Control GX. See the screenshot further down below in this manual. Enabling or disabling phase compensation is done in the Hub-4 settings on the Color Control GX. See the screenshot further down below in this manual.
  
-==== 3.2 Split- and three-phase inverter/charger system ====+==== 4.2 Split- and three-phase inverter/charger system ====
  
 === Installation details === === Installation details ===
Line 121: Line 126:
 In a multi-phase system, the charge current is configured per phase. There is not a total charge current which the system adheres too. This means that, for example when there is a relatively small battery bank, and a huge over production of PV on L1, and not on the other phases, only part of that over production on L1 will be used to charge the battery. In a multi-phase system, the charge current is configured per phase. There is not a total charge current which the system adheres too. This means that, for example when there is a relatively small battery bank, and a huge over production of PV on L1, and not on the other phases, only part of that over production on L1 will be used to charge the battery.
  
-===== 4Connecting and configuring the AC sensor ===== +===== 5Grid Meter =====
-A Hub-4 setup requires an AC sensor connected in the main distribution panel: between the grid and installation. This AC sensor has been designed for 3 phase measurement, but can be configured for single phase support as well.+
  
-=== 3-phase setup diagram=== +A Hub-setup requires an Energy Meter connected in the main distribution panelbetween the grid and installation. The meter is a three phase meter, but can be used for single phase installations as well.
-{{system_integration:em24_3P.png?300}}+
  
-=== single phase setup diagram=== +Follow the instructions in the [[:energy-meter|Energy Meter manual]].
-{{system_integration:em24_1P.png?300}}+
  
-Note the jumper between terminals 1 and 4. You do not need this connection if you have the version AV2 of the sensor. +===== 6. Multi/Quattro installation =====
- +
-=== Meter configuration ==+
-Change the front selector of the AC sensor so it is not in the locked state. This will allow the CCGX to automatically configure the meter. The front selector is located next to the display as indicated in the image below. +
- +
-{{system_integration:em24_front_selector.png?300}} +
- +
-=== Option A: Wireless connection to CCGX === +
- +
-1. Connect the Zigbee to USB converter to the CCGX using the supplied USB cable. A few seconds after connecting, the active LED should be on and the TX/RX LED should be blinking (the converter takes its power from the CCGX, so the CCGX needs to be switched on as well). +
- +
-{{system_integration:ZigbeeCoordinator.png?300}} +
- +
-2. Connect the Zigbee to RS485 converter to the EM24 energy meter: +
- +
-^ Converter ^ Grid meter ^ +
-| GND       | Terminal 43 | +
-| A         | Terminal 42 | +
-| B         | Terminal 41 | +
- +
-{{system_integration:ZigbeeRouter.png?300}}{{system_integration:EM24_Router.png?300}} +
-     +
-3. Make sure only one Zigbee device is powered up right now: the Zigbee to USB converter connected to the CCGX. Power down all others. //If you don't do this, the Zigbee to RS485 converter may be connected permanently to another Zigbee device.// +
- +
-4. Connect the 12V DC power supply to the Zigbee to RS485 converter. When the power is switched on, check the LEDs again. +
- +
-=== Option B: Wired connection to CCGX === +
-Connect the meter to the CCGX using the USB to RS485 converter cable: +
- +
-^ RS485 Converter ^ Grid meter ^ +
-| Yellow    | Terminal 41 | +
-| Orange    | Terminal 42 | +
-| Black     | Terminal 43 | +
-The Red, Green and Brown wire are not used +
- +
-{{system_integration:RS485_EM24.png?300}} +
- +
-===== 5. Multi/Quattro installation =====+
 Follow the instructions as per the standard installation manual that comes with the inverter/charger. Follow the instructions as per the standard installation manual that comes with the inverter/charger.
  
Line 176: Line 141:
   * (option) Connect MPPT Solar chargers to the DC side of the system. In this case make sure to either use a battery with built-in SOC, like an LG or BMZ battery, or add a BMV Battery monitor. And select that battery or battery monitor as the System Battery Monitor in the Settings -> System Setup Menu. Also keep the Sync SOC to VE.Bus option, a setting in that same menu, enabled.   * (option) Connect MPPT Solar chargers to the DC side of the system. In this case make sure to either use a battery with built-in SOC, like an LG or BMZ battery, or add a BMV Battery monitor. And select that battery or battery monitor as the System Battery Monitor in the Settings -> System Setup Menu. Also keep the Sync SOC to VE.Bus option, a setting in that same menu, enabled.
  
-===== 6. Multi/Quattro configuration =====+===== 7. Multi/Quattro configuration =====
 Steps: Steps:
   - Update the devices to the latest firmware version. Instructions [[updating_firmware:updating_ve.bus_products|here]].   - Update the devices to the latest firmware version. Instructions [[updating_firmware:updating_ve.bus_products|here]].
   - Use VEConfigure3 to add the self-consumption Hub-4 Assistant. Instructions on how to add an Assistant [[assistants:how_to_add_and_configure_an_assistant|here]].   - Use VEConfigure3 to add the self-consumption Hub-4 Assistant. Instructions on how to add an Assistant [[assistants:how_to_add_and_configure_an_assistant|here]].
 +
 +Notes with regards to the Input current limit and PowerAssist:
 +  * The Hub-4 Assistant will disable the PowerAssist setting in VEConfigure3. Please keep this option disabled. Note that the Hub-4 system will still PowerAssist, as it is part of the normal Hub-4 mechanism to power all loads, both connected before and after the Multi/Quattro, from the battery. Note that the regulation speed of Hub-4 is lower than PowerAssist. 
 +  * Input current limiter setting will work. The configured limit is used as the threshold for AC current at the ACin of the Multi/Quattro. For both directions of the current.
 +  * Do **not** enable the Dynamic current limiter setting in VEConfigure3
  
 Notes: Notes:
   * Whenever there is more PV power available than necessary to power the loads, the battery will be charged. Charge current and other parameters are configured on the Charger tab in VEConfigure3.   * Whenever there is more PV power available than necessary to power the loads, the battery will be charged. Charge current and other parameters are configured on the Charger tab in VEConfigure3.
-  * The Hub-4 Assistant will disable PowerAssist. Please keep this option disabled. 
   * Make sure to keep the lithium batteries checkbox on the charger page consistent with the battery choice in the Assistant.   * Make sure to keep the lithium batteries checkbox on the charger page consistent with the battery choice in the Assistant.
   * If you have a Multi Compact, check the DIP switches: DIP switch 1 must be on, and DIP switch 2 must be off.   * If you have a Multi Compact, check the DIP switches: DIP switch 1 must be on, and DIP switch 2 must be off.
-  * Do **not** enable the Dynamic current limiter setting in VEConfigure3 
  
-===== 7. Controlling depth of discharge =====+===== 8. Controlling depth of discharge =====
 //(Note: All absolute voltages mentioned in the text below are for a 12V system and should be multiplied by 2 or 4 for a 24V or 48V system.)// //(Note: All absolute voltages mentioned in the text below are for a 12V system and should be multiplied by 2 or 4 for a 24V or 48V system.)//
  
-When there is less PV power available than needed by the loads (a PV shortage, at night for example), energy stored in the battery will be used to power the loads. This continuous until the battery is considered empty. There are three parameters that check if the battery is empty: +When there is less PV power available than needed by the loads (a PV shortage, at night for example), energy stored in the battery will be used to power the loads. This continues until the battery is considered empty. There are three parameters that check if the battery is empty: 
-    - Battery State of ChargeMinimum state of charge is configured in the Color Control, and part of the [[#batterylife|BatteryLife algorithm]]. See section below+  - Battery State of ChargeMinimum SOC in the CCGX. When set to 60%all capacity between 60% and 100% will be used for to optimize self-consumption. And 0% to 60% will be used in case of a mains outage. The minimum SOC is parameter is configured in the CCGX. And it is also being updated daily by the [[#batterylife|BatteryLife algorithm]]. 
-    - Battery Voltage. See [[#dynamic_cut-off|Dynamic Cut-off section]], further down below. +  - Battery Voltage. See [[#dynamic_cut-off|Dynamic Cut-off section]], further down below. 
-    - Low cell signal from BMS+  - Low cell signal from a BMS: 
 +    * Victron VE.Bus BMS 
 +    * 3rd party Canbus enabled BMS
  
-The Sustain mode will be activated automatically __after__ the battery has been flagged as empty. See Sustain section below for more information.+__What about the Sustain mode?__
  
-Notes: +The Sustain voltages do not effect when the system stops discharging the batterySustain is activated only __after__ the battery has been flagged as emptySee Sustain section below for more information.
-  * the Minimum SOC threshold is only active while mains is connected. The threshold is ignored during inverter mode, ie. during a grid failure. only the other two parameters are usedDynamic cut-off and the low cell signal from the BMS. +
-  * it is also possible to set the minimum state of charge in the Hub-4 Assistant itself, but this is not recommended and we'll remove that option in the near futureUse the same setting in the Color Control GX instead.+
  
-==== Sustain Mode ==== +__What happens during a mains outage?__ 
-The purpose of the Sustain Mode is to prevent battery damage caused by leaving batteries in a deeply discharged stateThe Sustain Mode is entered after the battery has been discharged, see above.+  * Minimum Battery State of Charge is ignored 
 +  * Dynamic cut-off is still active 
 +  * Low cell signal from the VE.Bus BMS is still active 
 +  * Low cell signals from 3rd party canbus enabled BMS-es are ignored. System relies on the protection inside such a Lithium battery to trip.
  
-During Sustain Mode, the batteries will slowly be charged from the grid; maximum charge current is 5 Ampére. The Sustain level is 12.5V for lithium batteries. For non-lithium batteries, the sustain level is 11.5 V for the first 24 hours, and after that it is raised to 12.5 V.+__Configuring minimum state of charge in the Assistant or on the CCGX?__
  
-Excess solar power will also be used to charge the batteries. Sustain stops as soon as there has been sufficient excess solar power available to raise the battery voltage 0.1 V above the sustain level. Normal operation will then continue: solar deficits are complemented with power from the battery again.+It is possible to set the minimum state of charge in the Hub-4 Assistant itself, but this is not recommended and we'll remove that option in the near futureUse the same setting in the Color Control GX instead.
  
 ==== Dynamic Cut-off ==== ==== Dynamic Cut-off ====
Line 221: Line 192:
   * The Dynamic cut-off mechanism is in effect both when mains is available, and during a mains failure (system is in Inverter mode)   * The Dynamic cut-off mechanism is in effect both when mains is available, and during a mains failure (system is in Inverter mode)
  
 +==== Sustain Mode ====
 +The purpose of the Sustain Mode is to prevent battery damage caused by leaving batteries in a deeply discharged state. The Sustain Mode is entered after the battery has been discharged, see above.
 +
 +During Sustain Mode, the batteries will slowly be charged from the grid; maximum charge current is 5 Ampére. The Sustain level is 12.5V for lithium batteries. For non-lithium batteries, the sustain level is 11.5 V for the first 24 hours, and after that it is raised to 12.5 V.
 +
 +Excess solar power will also be used to charge the batteries. Sustain stops as soon as there has been sufficient excess solar power available to raise the battery voltage 0.1 V above the sustain level. Normal operation will then continue: solar deficits are complemented with power from the battery again.
  
-===== 8. Color Control GX configuration =====+===== 9. Color Control GX configuration =====
   - Power up the system.    - Power up the system. 
   - After a few seconds, the display will come to life. If not, check the wiring of the system.    - After a few seconds, the display will come to life. If not, check the wiring of the system. 
Line 231: Line 208:
  
 ==== BatteryLife ==== ==== BatteryLife ====
-The battery life feature prevents low battery state of charge over a long period. This may happen when there is insufficient PV power available to recharge the battery every day, for example in winter.  
  
-BatteryLife will make sure that, on average the battery will be recharged to 70 to 100% SOC, every day.+=== What does it do? === 
 + 
 +In case the expected Solar energy reduces, because of less sun shine, the system will automatically increase its low SOC limit. So that, with this reduced expected Solar Energy, the battery will still be fully charged at the end of the day to approx 100%. 
 + 
 +In case the expected Solar energy increased, because of more sun shine, the system will automatically decrease its low SOC limit. So that, with this increased expected Solar Energy, the battery will still be fully charged at the end of the day to approx 100%. 
 + 
 +Ask yourself, "Why should the battery be fully discharged, and stay that way? With as a result no reserve power in case of mains failure, and possible also a damaged battery"
 + 
 +=== Details === 
 + 
 +The BatteryLife feature prevents low battery state of charge over a long period. For example in winter, when there is insufficient PV power available to recharge the battery every day.  
 + 
 +BatteryLife ensures that, on averagethe battery will be recharged to 100% SOC, every day
 + 
 +It has several advantages: 
 +  * Operating in a partial state of charge is bad for lead acid battery life 
 +  * Certain lithium batteries need to be fully charged regularly, in order to balance. This includes the [[https://www.victronenergy.com/batteries/lithium-battery-12-8v|Victron 12.8V lithium batteries]], and therefore it is also mandatory to enable BatteryLife for those batteries. 
 +  * In case of mains failure, it is best to have spare energy available to power the loads from the battery. Continuously operating in a low state of charge serves no purpose.
  
 To do this we introduce a dynamic lower limit on the state of charge. Discharging is allowed only if the state of charge exceeds the limit. The limit is adjusted every day. On days with little or no surplus PV power the limit will be raised. And on 'good' days the limit is lowered again. To do this we introduce a dynamic lower limit on the state of charge. Discharging is allowed only if the state of charge exceeds the limit. The limit is adjusted every day. On days with little or no surplus PV power the limit will be raised. And on 'good' days the limit is lowered again.
Line 240: Line 233:
  
 This graphs shows a system in the spring, battery state of charge graphed over time. During the week progressing, more solar energy is becoming available, and you see the depth of discharge being increased. The red line shows how this system would operate without BatteryLife. This graphs shows a system in the spring, battery state of charge graphed over time. During the week progressing, more solar energy is becoming available, and you see the depth of discharge being increased. The red line shows how this system would operate without BatteryLife.
-{{ :ccgx:batterylife_comparison.png |}}+ 
 +{{ :ccgx:batterylife_comparison.png?800 |}} 
 ==== BatteryLife configuration ==== ==== BatteryLife configuration ====
  
 {{:ccgx:batterylifesettings2.png|}} {{:ccgx:batterylifesettings2.png|}}
  
-  * Actual state of charge limit:\\ The dynamic state of charge limit. Battery discharge will be disabled when the SoC reached this level. Hub-4 assistant settings (SoC stop level and dynamic cut-off) take priority to this limit. So discharge may be stopped before the limit is reached (sustain mode). The SoC stop level can be disabled safely when battery life is enabled.+  * Actual state of charge limit:\\ The dynamic state of charge limit. Battery discharge will be disabled when the SoC reached this level. Hub-4 assistant settings (SoC stop level and dynamic cut-off) take priority to this limit. So discharge may be stopped before the limit is reached (sustain mode). The SoC stop level can be disabled safely when BatteryLife is enabled.
   * Minimum state of charge limit:\\ The actual state of charge limit (and therefore the state of charge itself) will never be lowered below this limit.   * Minimum state of charge limit:\\ The actual state of charge limit (and therefore the state of charge itself) will never be lowered below this limit.
-  * The different Battery Life states are:+  * The different BatteryLife states are:
     * Self consumption: normal operation (discharge allowed)     * Self consumption: normal operation (discharge allowed)
     * Discharge disabled: the battery has been discharged to the actual SoC limit. The state will return to //self consumption// whenever the SoC rises 5%. When the system enters this state for the first time on a day, the actual SoC limit will be increased by 5%, and discharging will be allowed after the SoC has risen 10%.     * Discharge disabled: the battery has been discharged to the actual SoC limit. The state will return to //self consumption// whenever the SoC rises 5%. When the system enters this state for the first time on a day, the actual SoC limit will be increased by 5%, and discharging will be allowed after the SoC has risen 10%.
Line 253: Line 248:
  
 For further configuration of the Color Control GX, see its [[ccgx:start|manual]]. For further configuration of the Color Control GX, see its [[ccgx:start|manual]].
-===== 9. Using the Wired HUB-4 AC Sensor to measure PV Inverter output ===== 
-Instead of used for the Hub-4 regulation, the same three phase meter can be configured to measure output of a PV Inverter. Make sure to check Paragraph 1.3 in the [[ccgx:start|Color Control GX Manual]] for other options of measuring PV Inverter output. 
  
-Installation is similar to the AC sensor on the grid. Terminals 1, 4 and 7 should face the PV inverter. On the CCGX change the 'Role' of the meter to 'PV inverter'. You can now also chose its 'Position'. In the case of a Hub4 setup, this must be 'Input 1'. If you want to connect a single phase PV inverter to a 3-phase system connect all 3 phases to the grid phasing terminals (3, 6 and 9). Now you can chose on which phase you want the PV inverter by connecting the L1 line of the PV inverter to terminal 1, 4 or 7.+===== 11Troubleshooting =====
  
-There are 3 options to connect the extra AC sensor: +=== The system is not discharging ===
-    - Wired connection with an extra RS485 to USB converter cable. Works just like the grid meter. +
-    - Wired connection with modbus multidrop (both AC sensors connected to the same RS485 to USB converter cable). In this case you need to change the modbus address of one of the AC sensors (see below). +
-    - Wireless connection: the AC sensor is connected to an additional Zigbee to RS485 converter just like the grid meter. Also requires change of the modbus address.+
  
-Changing the modbus address: +  Is the battery already fully discharged? 
-    Press the joystick down until until the display shows 'Pass'. The joystick on the right side on the display, above the front selector). +  Is State of Charge at or below the [[#batterylife|BatteryLife]] level?  
-    Press the joystick down again and release immediately. +  Is the system in [[#sustain_mode|Sustain mode]]?
-    Press the joystick right several times until 'Address' appears. Press the joystick down. Now you can adjust the address by pressing the joystick up and down. Set it to 2. +
-    - Press down again. 'Baudrate' appears.  +
-    - Press down again twice. 'Address' appears again. +
-    - Press right until 'End' appears. +
-    - Press down. The display now shows measurements again.+
  
-On a single phase setup, you can use a single AC sensor to measure both grid and PV inverter. For wiring see the diagram below.+=== The system is not charging ===
  
-{{:system_integration:carlo-l1grid-l2pv.jpg|}}+  Is the battery already fully charged? 
 +  Is there a high load?
  
-On the CCGX go to the grid meter in the Wired AC sensor settings. Make sure 'Phase type' is set to 'Single phase' and 'PV inverter on phase 2' is enabled.+=== The system is in passthrough, not charging and not discharging ===
  
-{{:system_integration:ccgx-l1grid-l2pv.png|}}+Check the connection between the AC Sensor and the CCGX.
  
-===== 10. FAQ =====+===== 12. FAQ =====
 === What happens when the Multi does not receive data from the CCGX / Wired AC Sensor? === === What happens when the Multi does not receive data from the CCGX / Wired AC Sensor? ===
 It will switch to Bypass, and Sustain mode is still active and will prevent the battery from being discharged below, approximately, 50%. See Paragraph 6 for the details on Sustain and the Sustain Voltages. It will switch to Bypass, and Sustain mode is still active and will prevent the battery from being discharged below, approximately, 50%. See Paragraph 6 for the details on Sustain and the Sustain Voltages.
  
 === Is there a winter mode, like in Hub-2? === === Is there a winter mode, like in Hub-2? ===
-Yes.+No, but there is BatteryLife.
  
 === VEConfigure keeps giving the warning 'Device must be reset' === === VEConfigure keeps giving the warning 'Device must be reset' ===
Line 317: Line 303:
   * Both Solar Charge Controllers with a VE.Can communication port as well as with a VE.Direct communication port can be used.   * Both Solar Charge Controllers with a VE.Can communication port as well as with a VE.Direct communication port can be used.
   * There is no VE.Bus to VE.Can interface cable required, also it is not required to set absorption and float voltages in the mppt higher than the same in the Multi or Quattro.   * There is no VE.Bus to VE.Can interface cable required, also it is not required to set absorption and float voltages in the mppt higher than the same in the Multi or Quattro.
 +
  
 ===== DISQUS ===== ===== DISQUS =====
 ~~DISQUS~~ ~~DISQUS~~
 +
system_integration/hub4_grid_parallel.1472212342.txt.gz · Last modified: 2016-08-26 13:52 by mvader

Donate Powered by PHP Valid HTML5 Valid CSS Driven by DokuWiki