multiplus_faq
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
multiplus_faq [2022-09-20 02:24] – [Software Settings] guystewart | multiplus_faq [2023-02-16 01:50] (current) – guy_stewart | ||
---|---|---|---|
Line 109: | Line 109: | ||
- | ===== 1.5 Loss of mains detection (LOM) ===== | + | ===== 1.5 Loss of mains detection (LOM) (Only applicable to ESS systems) ===== |
+ | |||
+ | This part is only applicable on systems where a grid-code is selected (generally only ESS systems) on an off-grid system a grid code should not be used and in the selection box for grid code, ' | ||
Loss of mains detection will push and pull at voltage and frequency to see if there is still a generating source. This process can cause issues with some generators, or high impedance connections to generators. | Loss of mains detection will push and pull at voltage and frequency to see if there is still a generating source. This process can cause issues with some generators, or high impedance connections to generators. | ||
Line 196: | Line 198: | ||
If you have a small generator and have trouble getting connected or staying connected, Disable PowerAssist to allow the device to reduce the AC input current limit. | If you have a small generator and have trouble getting connected or staying connected, Disable PowerAssist to allow the device to reduce the AC input current limit. | ||
+ | ====== 5. Generator control in 3 phase and parallel systems ====== | ||
+ | |||
+ | There is some specific and non-intuitive conditions when setting AC input current limits, and Charge Current limits for Large systems that involve more than one MultiPlus, and/or a GX device. | ||
+ | |||
+ | Those specific details are articulated here: | ||
+ | https:// | ||
+ | |||
+ | Described in the online training theory here: | ||
+ | @ 38 minutes and 43 seconds - https:// | ||
+ | Demonstrated in the 3 phase installation training here: | ||
+ | @ 25 minutes - https:// | ||
====== Still not connecting? ====== | ====== Still not connecting? ====== | ||
Line 250: | Line 263: | ||
- | ===== DISQUS ===== | ||
- | ~~DISQUS~~ |
multiplus_faq.1663633460.txt.gz · Last modified: 2022-09-20 02:24 by guystewart